3)Select [OK] button.

Click the [OK] button after fully completing the ventilation unit interlocking setting.

Note:

When the ventilation unit interlocking setting is changed on the interlocked setting screen, it is possible to reflect the changed contents on the G-50A system .

It is possible to set up to 16 indoor units to one interlocking ventilation unit.

When the [OK] button is clicked, the screen to confirm whether the ventilation unit interlocking setting is completed, is displayed.

8.7Monitoring Screen Set-up

Set the information such as the floor name, plan view, operation block, or other items to be monitored/ displayed on the management screen of the integrated centralized control software TG-2000A.

8.7.1 Configuration Procedure and Restrictions

Check these points before setting the system configuration.

[Procedure]

1)Click the [Monitoring screen set -up] button. Click the [Monitoring screen set-up] button in the User Settings Group in the Initial window.

2)Click the [OK] button after checking the display contents.

Check the information displayed and click the [OK] button.

*When the [Cancel] button is clicked, this setting is terminated to return to the initial screen.

The monitor display set-ups are done in the following

order.

Step1 : Set -up of model nameMonitoring screen set-up preparation screen

Step 2 : Set-up of the number of floors, and floor name

Step 3 : Creation of a plane view

Step 4 : Set -up of floor name and G-50

Step 5 : Set -up of icon arrange and name

Step 6 : Set -up of block

8.7.2 Set-up of model name (Step 1)

G-50A setting button

Set the model name of the air conditioner unit (outdoor unit, indoor unit, sub unit, LOSSNAY etc.) connected to this system.

Note:

The Charge function use this set Model name data. When the model name is changed, the data is updated and control is carried out using that data.

The Model name can be checked during maintenance.

Setup the unit configuration model name

 

 

[Procedure]

 

 

 

 

1)

Click the “ / ” button to select G-50

No.

 

 

 

 

Set-up of model name screen

 

 

Select the G-50A No. to be assigned using the

 

 

 

 

 

“ / ” buttons.

 

 

Set button

 

2)

Select the unit to be set .

 

 

Model name candidate

Click the units for which the same Model Name is to be set. The selected cells are displayed in cyan

and become the objective of Model Name setup. Each time clicked, the unit is alternately selected and removed. Multiple units can also be selected.

34

Page 37
Image 37