No.6

STP-H600/H1000 Series Instruction Manual

PROCEDU

Lamp Being Lit

Probable Causes

Countermeasures

Referred

RE No.

 

 

 

Section

No.6

“FAILURE”

(1) Insufficient charge or

1) Check whether or not the

9

 

“BATTERY NG”

deterioration of the

battery is fully charged. If

10

 

(inside the front

battery.

the battery is not

 

 

panel)

 

sufficiently charged, charge

 

 

( “EMERGENCY

 

 

 

 

it.

 

 

OPERATION”

 

 

 

 

2) Check the deterioration and

 

 

lamp may light)

 

 

 

 

the replacement date of the

 

 

 

 

 

 

 

 

battery. If the battery has

 

 

 

 

deteriorated or the

 

 

 

 

replacement date has

 

 

 

 

passed, replace the battery

 

 

 

 

with a new one.

 

 

 

 

3) After taking steps 1) and 2)

 

 

 

 

above, reset BATTERY NG.

 

Manual backgroundManual background CAUTION Manual background

When checking the " BATTERY NG" lamp, turn OFF the primary power (Switch the breaker "OFF"), then open the front panel. After opening the front panel, turn ON the primary power (Switch the breaker "ON"). Failure to do so may result in electric shock of product damage due to short-circuiting of the internal circuit.

Manual backgroundNOTICEManual backgroundManual backgroundManual background

The "BATTERY NG" lamp remains lit until it is reset even after the primary power is turned OFF (the breaker is switched "OFF").

15-8

Page 112
Image 112
Seiko Instruments MT-17E-003-D instruction manual No.6