STP-H600/H1000 Series Instruction Manual

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminal

 

 

 

Description

 

 

 

 

 

 

 

 

 

 

Terminal for connecting the air cooling unit.

(6)

 

 

FAN

(5)

The voltage input to AC. POWER terminal ((19)-(20)) is

 

 

output to this terminal when the STP pump is in acceleration

 

 

 

 

 

 

 

 

 

 

or rated operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

N.O OUT

 

 

 

The voltage is cut OFF when the STP pump is under the

 

 

 

 

 

 

BRAKE state (See Section 7.2.2, “Air Cooling Method").

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminal for outputting the POWER ON state signal.

(8)

 

POW ER

(7)

This terminal is closed when the magnetic bearing functions

 

and the rotor levitates.

 

 

 

N.O OUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminal for outputting the ALARM signal.

(10) ALARM OUT (9)

When an abnormality/error is detected under the POWER ON

state, the terminal between (10)-(9) is closed, and the

 

COM

N.O

 

terminal between (10)-(11) is opened.

 

 

 

 

 

 

 

 

 

 

N.C

 

 

 

 

 

 

 

 

 

 

 

(11)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(12)

 

 

 

 

 

 

 

Terminal for outputting the BRAKE state signal.

 

 

BRAKE

N.O OUT

This terminal is closed when the STP pump is in brake.

 

 

 

 

 

 

 

 

(14)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminal for outputting the NORMAL OPERATION state

 

 

NORM OUT (13)

signal.

 

 

When the STP pump is in rated operation, the terminal

 

 

 

 

 

 

 

N.O

 

between (16)-(13) is closed, and the terminal between (16)-

(16) COM N.C

 

 

 

(15) is opened.

(15)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminal for outputting the ACCELERATION state signal.

(18)

 

POW ER

(17)

This terminal is closed when the STP pump is in acceleration.

 

 

 

N.O OUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8-2