Library Specifications
| 
 | Library Specifications | ||
| TABLE  | 
 | ||
| 
 | 
 | ||
| Physical | 
 | ||
| 
 | 
 | ||
| • Hmeight | 2.37 m (236.6 cm) or 7.76 ft (93.15 in.) | ||
| • Width | 1.7 m (170.8 cm) or 5.6 ft (67.25 in.) | ||
| • Depth (Base Library) | 2.8 m (276.9 cm) or 9.1 ft (109 in.) | ||
| 3.7 m (372.1 cm) or 12.2 ft (146.5 in.) | |||
| ■ With 1 expansion module | |||
| 4.7 m (467.4 cm) or 15.3 ft (184 in.) | |||
| ■ With 2 expansion modules | |||
| 5.6 m (562.6 cm) or 18.5 ft (221.5 in.) | |||
| ■ With 3 expansion modules | |||
| 
 | |||
| 
 | 
 | ||
| • Weights | Library only: | ||
| ■ | Base Library | 1954 kg (4,309 lb) | |
| ■ With 1 expansion module | 2392 kg (5,274 lb) | ||
| ■ With 2 expansion modules | 2830 kg (6,239 lb) | ||
| ■ With 3 expansion modules | 3396 kg (7,487 lb) | ||
| • Weight distribution per pad | 454 kg (1,000 lb) | ||
| 
 | 
 | ||
| •  | 231 cm (91 in.) | ||
| ■ | Height | ||
| ■ | Width | 17.2 cm (6.76 in.) | |
| ■ | Depth | 150.8 cm (59.4 in.) | |
| ■ | Weight | 121 kg (266 lb) including the mechanisms | |
| 
 | 
 | ||
| • Service Clearances | 
 | ||
| ■ | Customer Interface Module | 66 cm (26 in.) | |
| ■ Drive & Electronics Module | 85 cm (33.5 in.) | ||
| ■ | 15.24 cm (6 in.) | ||
| 
 | 
 | ||
| • Temperature | 
 | ||
| ■ | Operating | +16 to +32°C (+60 to +90°F) | |
| ■ | Shipping | ||
| ■ | Storing | +4.4 to +32°C (+40 to +90°F) | |
| 
 | 
 | +25.6°C (+78°F) maximum,  | |
| 
 | 
 | ||
| • Wet bulb (operating) | 
 | ||
| ■ | Humidity | 20% to 80% | |
| ■ | Operating | 5% to 90% | |
| ■ | Shipping | 20% to 80% | |
■Storing
| • Operating Heat Output | 44,380 Btu/hr (maximum loading**) | 
| 
 | Calculation for this is: 3.41214 x Watts = Btu/hr | 
• Power Consumption
Single phase configuration and three phase configurations
13.0kW (maximum loading**)
13.7kVA
kVA = kWatts ÷ Power factor
The power factor for the SL8500 = 0.95
**Maximum loading includes 64 tape drives, 4 fully loaded racks, 8 HandBots, all the front frame components (CAPs, service door, and elevators), plus redundant control modules.
| 96154 • Revision K | Chapter 1 Introduction 25 | 