SwitchBlade x8106 Chassis Switch Installation Guide

Powering On the AT-SBxPWRSYS1 DC System Power Supply

This section contains instructions on how to power on the AT- SBxPWRSYS1 DC Power Supply. For installation instructions, refer to “Installing the AT-SBxPWRSYS1 DC Power Supply” on page 103.

The power supply unit has a ground connection and positive and negative DC terminals. You may install the ground and power lead wires with the terminal lugs that come with the unit or with bare wire. The wire requirements are slightly different for terminal installation versus bare wire installation. Here are the wire requirements if you are using the terminal lugs that come with the power supply:

Two 8 AWG stranded power wires (not provided)

One 10 AWG stranded grounding wire (not provided)

Here are the wire requirements for bare wire installation:

Two 8 AWG solid or stranded power wires (not provided)

One 10 AWG solid or stranded grounding wire (not provided)

Here is a list of the required tools:

Crimping tool (not provided)

8 mm wrench (not provided)

#1, #2, and #3 Phillips-head screwdrivers (not provided)

#3 Phillips-head 30 to 40 inch-lbs Phillips-head torque screwdriver (optional - not provided)

Here are the procedures for powering on the AT-SBxPWRSYS1 DC

Power Supply:

“Choosing a Method for Attaching the Grounding Wire” on page 153

“Connecting the Grounding Wire with the Grounding Terminal” on page 153

“Connecting the Grounding Wire with Bare Wire” on page 156

“Choosing a Method for Attaching the Power Wires” on page 158

“Connecting the DC Power Wires with the Straight Terminals” on page 158

“Connecting the DC Power Wires with the Right Angle Terminals” on page 167

“Connecting Bare DC Power Wires” on page 173

151

Page 151
Image 151
Allied Telesis X8106 manual Powering On the AT-SBxPWRSYS1 DC System Power Supply