Facility requirements | A |
TABLE 16 System FRU weights (Continued)
FRU | Weight |
|
|
Cable management device | 0.45 kg (1.0 lb) |
|
|
Chassis door | 2.09 kg (4.6 lb) |
|
|
Facility requirements
The facility where the Brocade DCX
•Adequate supply circuit, line fusing, and wire size, as specified by the electrical rating on the chassis nameplate.
•The environmental specifications listed in Environmental requirements.
•The power specifications listed in Power specifications.
Furthermore, if the Brocade DCX
•All equipment installed in the rack has a reliable branch circuit ground connection, and does not rely on a connection to a branch circuit, such as a power strip.
•The rack is balanced and mechanically secured to provide stability in the event of an earthquake.
•Additional equipment does not exceed the rack’s weight limits.
Environmental requirements
Table 17 lists the environmental operating ranges for the Brocade DCX
TABLE 17 | Environmental requirements |
| |
|
|
|
|
Condition |
| Acceptable range during operation | Acceptable range during nonoperation |
|
|
| |
Ambient temperature | 0° to 40° C outside switch | ||
|
| (32° to 104° F) | |
|
|
|
|
Humidity |
| 5% to 85% RH noncondensing, at | 10% to 90% RH noncondensing, at 70° |
|
| 40° Celsius, with maximum gradient of | Celsius |
|
| 10% per hour |
|
|
|
|
|
Altitude |
| Up to 3 km (10,000 ft.) | 0 to 12 km (40,000 ft.) |
|
| above sea level | above sea level |
|
|
|
|
Shock |
| 20G, 6ms duration, | 33G, 11ms duration, |
|
|
|
|
Vibration |
| 0.5G | 2.0G |
|
|
| octave/minute |
Brocade DCX | 113 |
|