4 Determining the status of a blower assembly
1 Power LED
FIGURE 15 Power supply
Table 6 describes the power supply LED patterns and the recommended actions for those patterns.
TABLE 6 Power supply LED descriptions
LED purpose | Color | Status | Recommended action |
Power | No light | Power supply does not have |
| (LED is off) | incoming power and is not |
|
| providing power to the Brocade |
|
| DCX |
Ensure that the power supply is firmly seated, the Brocade DCX
| Steady green | Power supply has incoming | No action required. |
|
| power and is providing power to |
|
|
| the Brocade DCX |
|
|
|
|
|
| Flashing green | Power supply is about to fail. | Replace the power supply. |
|
|
|
|
Determining the status of a blower assembly
Complete the following steps to determine the status of a blower assembly.
1.Check the LED indicators on the blower assembly (see the following figure). The LED patterns may temporarily change during POST and other diagnostic tests; for information about how to interpret the LED patterns, refer to Table 7. The Brocade DCX
2.Check the blower assembly status using the fanShow command.
The status for each blower assembly displays OK, Absent, or Faulty. The RPM of each fan in the assembly is also provided. If a blower assembly displays absent or faulty, contact the Brocade DCX
Figure 16 shows the blower assembly.
54 | Brocade DCX |
|