Preparing for Brocade DCX | 2 |
The following steps are required to ensure correct installation and operation. 1.
Plan to install the Brocade DCX
2.Ensure that dedicated electrical branch circuits with the following characteristics are available:
NOTE
Refer to “Power specifications” on page 114 for specific requirements depending on your chassis configuration.
•
•
•cables for 200 - 240 VAC service; up to cables for 110 - 120 VAC service
•Protected by a circuit breaker in accordance with local electrical codes
•Supply circuit, line fusing, and wire size adequate to the electrical rating on the chassis nameplate
•Location close to the chassis and easily accessible
•Grounded outlets installed by a licensed electrician and compatible with the power cords
ATTENTION
To maximize fault tolerance, connect each power cord to a separate power source.
3.Plan for cable management before installing the chassis.
Cables can be managed in a variety of ways, such as by routing cables below the chassis, to either side of the chassis, through cable channels on the sides of the cabinet, or by using patch panels.
4.Ensure that the following is available for configuration of the Brocade DCX
•Workstation with an installed terminal emulator, such as HyperTerminal
•Serial cable (provided)
•Three Ethernet cables (including one spare)
•Access to an FTP server for backing up the switch configuration or collecting supportsave output data (optional)
•A Brocade USB stick for collecting supportsave output data (optional)
•Transceivers (copper and optical) and compatible cables
5.Ensure that the air intake and exhaust vents have a minimum of 5.1 cm (2 in.) of airspace.
6.Ensure that the air temperature on the air intake side is less than 40°C (104°F) during operation.
Brocade DCX | 15 |
|