Chapter 3 Installing the Cisco XR 12410 Router

Connecting Power to the Router

Connecting Power to an AC-Powered Router

Use the following procedure to connect the AC power cords to the router.

Note Connect each AC power supply to a dedicated power source (branch circuit). Each AC-input power supply operates between 200 and 240 VAC and requires at least a 20 A service for North American use, or a 13 A service for international use. For more information on AC power cords, see the “Power Connection Guidelines” section on page 2-13.

Step 1 Connect each power cable to the AC power connector on the horizontal trough and secure them with their retention clips (Figure 3-30).

Step 2 Plug each power supply cable into its AC outlet.

Figure 3-30 Connecting Source AC to the AC-Input Power Connector