Object 0x6075: Motor Rate Current

CANopen DSP 402 Implementation Guide

MAN-CAN402IG (Ver. 1.2)

106

Object 0x6075: Motor Rate Current

This value is taken from the motor nameplate and is entered in multiples of milliamp. Depending on the motor and drive technology this current may be either DC, peak or rms (root-mean-square) current. All relative current data refers to this value.

Object description:

 

Index

 

6075h

 

Name

 

Motor Rate Current

 

Object code

 

VAR

 

Data type

 

UNSIGNED32

 

Category

 

Mandatory

Entry description:

 

 

 

 

 

 

 

Access

 

Read/write

 

PDO mapping

 

No

 

Value range

 

UNSIGNED32

 

Default value

 

0

Note: This value of 6075h is set to CL[1] after it is converted to Amperes.

Object 0x6076: Motor Rate Torque

This value is taken from the motor name plate and is entered as a multiple of mNm (mill wtonmeter). All relative torque data refer to this value.

For linear motors, the object name is not changed, but the motor rated force value must be entered as a multiple of mN (mill Newton)..

Object description:

 

Index

 

6076h

 

Name

 

Motor Rate Torque

 

Object code

 

VAR

 

Data type

 

UNSIGNED32

 

Category

 

Mandatory

Entry description:

 

 

 

 

 

 

 

Access

 

Read/write

 

PDO mapping

 

No

 

Value range

 

UNSIGNED32

 

Default value

 

0