9.4DSP 402 Homing Methods

CANopen DSP 402 Implementation Guide

MAN-CAN402IG (Ver. 1.2)

60

9.4DSP 402 Homing Methods

The following sub-sections describe the details of how each homing mode functions. The Elmo drives support each of these methods.

9.4.1Method 1: Homing on the negative limit switch and index pulse

Using this method, the initial direction of movement is leftward if the negative limit switch is inactive (here shown as low). The home position is at the first index pulse to the right of the position where the negative limit switch becomes inactive.

Figure 9-1:Homing on the negative limit switch and index pulse

9.4.2Method 2: Homing on the positive limit switch and index pulse

Using this method, the initial direction of movement is rightward if the positive limit switch is inactive (here shown as low). The position of home is at the first index pulse to the left of the position where the positive limit switch becomes inactive.

Figure 9-2:Homing on the positive limit switch and index pulse