D 3: Line Voltage Performance Report

 

Model 500/600

5-3. DIAGNOSTIC MODE

D 3: Line Voltage Performance Report

DETAILS (Continued)

This section displays information about how good the line voltage

 

supply has been for the present day and for the present batch of oil.

 

The controller continually monitors the line voltage supplied to the fryer

 

(when the fryer is on). If the line voltage drops below [90%] of its

 

nominal value, the controller signals a “LOW VOLTAGE” alarm. This

 

alarm sounds at the end of each Cook Cycle for which low voltage has

 

been detected. While not cooking, the low voltage alarm can sound as

 

frequently as every 30 minutes.

[ ]” around a value, such as [90%], means this value is programmable and might change with later software versions.

Voltage Report for Today

If no low voltage warnings have been detected for the present day, the controller shows, “D3: VOLTAGE OK, D3: TODAY “

If one or more low voltage warnings have been detected for the present day, the following sequence example could be displayed:

“D3: YOU HAD 3”

“D3: LOW VOLTAGE”

“D3: WARNINGS”

“D3: TODAY”

(Press DETAILS (Continued) )

“D3: MIN VOLTAGE”

“D3: TODAY = 83%”

(Press Voltage Report for Today )

“D3: MAX VOLTAGE”

“D3: TODAY = 101%”

(Press “D3: YOU HAD 3” )

303

5-13

Page 69
Image 69
Henny Penny 500, 600 D 3 Line Voltage Performance Report, DETAILS Continued, Voltage Report for Today, Diagnostic Mode