DEFINITY Enterprise Communications Server Release 6
Maintenance for R6vs/si
555-230-127 Issue 1
August 1997
Maintenance Object Repair Procedures
Page10-388DC-POWER
10
"DEFINITY AUDIX System Power Procedures" in Chapter 5, "Routine Maintenance Procedures", on the circuit pack, and in DEFINITY AUDIX documentation.
Error Log Entries and Test to Clear Values
System Technician-Demanded Tests:
Descriptions and Error Codes
Always investigate tests in the order presented in the following table. By clearing
error codes associated with the
Single-Carrier Cabinet Power Query Test
, for
example, you may also clear errors generated from other tests in the testing
sequence. Test descriptions and recommended maintenance procedures follow
for all errors that can occur during system technician-demanded testing.
Notes:
a. Refer to “EMG-XFER” for a description of this test.
b. Refer to “EXT-DEV” for a description of this test.
c. Refer to “RING-GEN” for a description of this test.
1. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the
appropriate test description and follow the recommended procedures.
1. D = Destructive; ND = Nondestructive
Table 10-126. Single-Carrier Cabinet Power Error Log Entries
Error
Type Aux
Data Associated Test Alarm
Level On/Off
Board Test to Clear Value
010 Any Any Any test environment P sh r 1
513 0 Single-Carrier Cabinet MAJOR ON test environment P r 2
Power Query Test (#79)
Order of Investigation Short Test
Sequence Long Test
Sequence D/ND1
Single-Carrier Cabinet Power Query Test (#79) X X ND
Emergency Transfer Query Test (#124) (a) X X ND
External Alarm Lead Query Test (#120) (b) X X ND
Analog Ring Generator Initialization Test (#117) (c) X X ND
Analog Ring Generator Query Test (#118) (c) X X ND