DEFINITY Enterprise Communications Server Release 6
Maintenance for R6vs/si
555-230-127 Issue 1
August 1997
Maintenance Object Repair Procedures
Page10-1302TBRI-TRK (TN2185 ISDN Trunk-Side BRI)
10
System Technician-Demanded Tests:
Descriptions and Error Codes
Always investigate tests in the order presented in the table below when
inspecting errors in the system. By clearing error codes associated with the

Services State Test

, for example, you may also clear errors generated from other
tests in the testing sequence.
Signaling Link State (#1251)
This test is non-destructive.
This test checks the current state of the signaling link. The test looks at the
board-level translations, checks that the board is physically inserted, gets the
state of the D-Channel and service state of the port.
The test passes if the signaling link (D-Channel) is connected and operating
normally. The test fails if the board is not installed, the signaling link is
disconnected, or if the port is out of service. The test aborts otherwise.
1. Destructive; ND = Nondestructive
Order of Investigation Short Test
Sequence Long Test
Sequence D/ND1
Signaling Link State Check Test (#1251) X X ND
Service State Audit Test (#256) X X ND
Call State Audit Test (#257) X X ND
ISDN Test Call Test (#258) X ND
Table 10-450. TEST #1251 Signaling Link Sta te Test
Error
Code Test
Result Description/ Recommendation
ABORT Internal system error
1018 ABORT The test is disabled.
1. Enable the test by entering “enable test #1251”.
1114 ABORT The signaling link is in a transitional state.
1. Retry the command at 1-minute intervals a maximum of 5 times.
Continued on next page