DEFINITY Enterprise Communications Server Release 6
Maintenance for R6vs/si
555-230-127 Issue 1
August 1997
Maintenance Object Repair Procedures

Page10-1097RING-GEN (Analog Ring Generator)

10
Hardware Error Log Entries and Test to Clear
Values
System Technician-Demanded Tests:
Descriptions and Error Codes

Always investigate tests in the order presented in the following tables when

inspecting errors in the system. By clearing error codes associated with the

Analog Ring Generator Initialization Test

, for example, you may also clear errors

generated from other tests in the testing sequence.
1. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the
appropriate test description and follow the recommended procedures.
1. D = Destructive; ND = Nondestructive
Analog Ring Generator Error Log Entries
Error
Type Aux
Data Associated Test Alarm
Level On/Off
Board Test to Clear Value
010 Any Any Any test environment UU
1 Analog Ring Generator Query
Test (#118) MAJOR ON test environment UU r 3
Multicarrier Cabinet
Order of Investigation Short Test
Sequence Long Test
Sequence D/ND1
Analog Ring Generator Initialization Test (#117) X X ND
Analog Ring Generator Query Test (#118) X X ND
Battery & Battery Charger Query Test (#5) (a) X X ND
AC Power Query Test (#78) (b) X X ND
Power Unit Query Test (Carrier E) (#127) (c) X X ND
Power Unit Query Test (Carrier D) (#127) (c) X X ND
Power Unit Query Test (Carrier A) (#127) (c) X X ND
Power Unit Query Test (Carrier B) (#127) (c) X X ND
Power Unit Query Test (Carrier C) (#127) (c) X X ND
Emergency Transfer Query Test (#124) (d) X X ND
Cabinet Sensors Query Test (#122) (e) X X ND
External Alarm Lead Query Test (#120) (f) X X ND