DEFINITY Enterprise Communications Server Release 6
Maintenance for R6vs/si
555-230-127 Issue 1
August 1997
Maintenance Object Repair Procedures

Page10-690HYB-LINE (Hybrid Line)

10
Hybrid Line Remote Digital Loop Around Test (#59)

This test checks the digital control pair from the port circuit to the terminal. The

on-board microprocessor sends a message to the terminal and checks for a

proper return message. This test is repeated three times, with two out of the three

attempts passin g being sufficien t for this test to pa ss. [G1] This tes t will run if the

station is in-service or out-of-service.

0NO
BOARD The test could not relate the internal ID to the port (no board). This could
be due to incorrect translations, no board i s inserted, an incorrect board is
inserted, or an insane board is inserted.
1. Check to ensure that the board translations are correct. Use the list
config command, and resolve any problems that are found.
2. If the board was found to be correctly inserted in step 1, issue the
busyout board command.
3. Issue the reset board command.
4. Issue the release busy board command.
5. Issue the test board long command. This should re-establish th e
linkage between the internal ID and the port. If this is not the case,
dispatch to check to ensure that there is a valid board inserted.
Table 10-230. TEST #59 Hybrid Line Remote Digital Loop Around Test
Error
Code Test
Result Description/ Recommendation
ABORT Internal System Error.
1. Retry the command at 1-minute intervals for a maximum of 5 times.
2. If the test continues to abort, escalate the problem.
Continued on next page
Table 10-229. TEST #58 Hybrid Line Local Digital Loop Around Test — Continued
Error
Code Test
Result Description/ Recommendation
Continued on next page