Operation of system alarm display

(1)System alarm display resetting

Touch

1. Eliminate each cause of the system alarm being occurred.

Error causes can be identified by the error code, error message and channel No. displayed on the System alarm screen.

( 18. TROUBLESHOOTING)

2. A method for resetting system alarm depends on an error.

GOT error

Touch [Reset] button to reset system alarms.

CPU error and Network error

The system alarm is automatically reset after its cause is eliminated.

POINT

(1)Before resetting the system alarm display in the GOT error

Eliminate the system alarm cause before resetting the system alarm display in the GOT error.

If not eliminated, the system alarm display in the GOT error will not be reset even after the reset operation.

(2)Processings with reset operation

The following data in the system information are also reset.

GOT error code (Write device)

GOT error detection signal (System Signal 2-1.b13)

14 - 20

14. GOT SELF CHECK (DEBUG AND SELF CHECK)

 

14.3 System Alarm Display