18.2.2List of error message/system alarm

The system alarm detected with GOT is shown below.

Error

Error message

 

Action

Channel No.

code

 

storage

 

 

 

 

Set monitor points too large.

Decrease the number of objects from the displayed screen.

 

303

For the number of maximum objects for 1 screen, refer to the following.

 

Decrease setting points.

 

GT Designer3 Version1 Screen Design Manual (Fundamentals)

 

 

 

 

 

 

 

 

 

 

 

Set trigger points too large.

The number of objects using Sampling/Cycle during ON/Cycle during

 

304

OFF exceeds 100.

 

Decrease setting points.

 

 

 

Decrease the number of objects.

 

306

No project data.

The project data is not downloaded or the screen data is not sufficient.

 

Download screen data.

Download the project data or screen data.

 

 

 

 

 

 

307

Monitor device not set

The monitor device of the object is not set.

 

Set the monitor device of the object.

 

 

 

 

 

 

 

 

 

308

No comment data.

The comment file does not exist.

 

Download comment.

Create the comment file and download to GOT.

 

 

 

 

 

 

309

Device reading error.

The error occurred when reading a continuous device.

 

Correct device.

Correct the device.

 

 

 

 

 

 

 

 

 

• Specified base screen / window screen does not exist in the project

 

310

Project data does not exist or out

 

data.

 

of range.

 

• Specified base screen / window screen is out of the permissible area.

 

 

 

 

Specify the existing base screen / window screen.

 

 

 

 

 

 

 

No. of alarm has exceeded

The number of alarm histories that can be observed by the alarm history

 

311

upper limit.

display function has exceeded the maximum points.

 

 

Delete restored alarm.

Delete the restored history to decrease the number of alarm histories.

 

 

 

 

 

 

 

 

The collection frequency exceeded the upper limit when "Store Memory"

 

 

No. of sampling has exceeded

and "Accumulate/Average" were set in the scatter graph.

 

312

upper limit.

 

• Approve "Clear trigger" setup in the scatter graph.

 

 

Delete collected data.

 

• Set the "Operation at frequency over time" to "Initialize and Continue"

 

 

 

 

in scatter graph.

 

 

 

 

 

 

315

Device writing error.

Error occurred while writing in the device.

 

Correct device.

Correct the device.

 

 

 

 

 

 

 

Cannot display or input operation

In indirect specification of comment/parts number, the data operation

 

 

result exceeded the range in which device type can be expressed.

 

316

value.

 

Review the data operational expression, in order not exceeding the range

 

 

Review expression.

 

 

in which the device type can be expressed.

 

 

 

 

 

 

 

 

 

 

 

Data of an object, to which [Collect data only when trigger conditions are

 

 

 

satisfied] is set, are collected too frequently, or the number of objects has

 

 

Too high frequency of data

exceeded the number of objects collectable simultaneously.

 

317

collection.

Set a longer cycle for trigger occurrence to each object.

 

 

Review conditions.

Make the settings so that 257 or more display triggers of objects, to which

 

 

 

[Collect data only when trigger conditions are satisfied] is set, do not

 

 

 

occur simultaneously.

 

 

 

 

 

 

320

Specified object does not exist or

The part file does not exist.

 

out of range.

Create the part file and download to GOT.

 

 

 

 

 

 

 

 

The monitored device No. is out of the permissible area of the targeted

 

322

Dedicated device is out of range.

PLC CPU.

 

Confirm device range.

Set the device within the range that can be monitored by the monitored

 

 

 

PLC CPU and parameter settings.

 

 

 

 

 

 

17

INSPECTION

MAINTENANCE AND

18

APPENDICESTROUBLESHOOTING

18. TROUBLESHOOTING

18 - 13

18.2 Error Message and System Alarm