*1 Bright dots (always lit) and dark dots (unlit) may appear on a liquid crystal display panel due to its characteristics. It is impossible to completely avoid this symptom, as the liquid crystal display comprises of a great number of display elements. Flickers may be observed depending on the display color.
Please note that these dots appear due to its characteristic and are not caused by product defect.
Flickers and partial discoloration may be generated on the liquid crystal display panel due to the display contents or the contrast adjustment. However, please note that these phenomena appear due to its characteristic and are not caused by product defect. There is a difference in the display brightness and the color tones between liquid crystal display panels. When using multiple liquid crystal display panels, please note that there is an individual difference between them.
A crosstalk (shadow as an extension of the display) may appear on the liquid crystal display panel. Please note that it appears due to its characteristic.
When the display section is seen from the outside of the display angle, the display color seems like it has changed. Please note that it appears due to its characteristic. Especially, the response time of a STN liquid crystal display is slower in the lower temperature due to its characteristic. Please use the display after checking the response time.
Please note that the response time, brightness and color of the liquid crystal display panel may vary depending on the usage environmental temperature.
When the same screen is displayed for a long time, an incidental color or partial discoloration is generated on the screen due to heat damage, and it may not disappear.
To prevent the heat damage, the screen saver function is effective. For details on the screen saver function, refer to the following.
*2 Gradation inversion is a characteristic of liquid crystal display panel. Please be forewarned that depending on the displayed color, the visualization may be difficult even within the described view angle.
*3 The GOT screen saving/backlight off function prevents images from becoming permanently etched on the display screen and increases the backlight life.
*4 The touch panel is analog resistive
Do not press the GOT display section with a pointed material as a pen or driver. Doing so can result in a damage or failure of the display section.
An analog resistive
*5 ROM in which new data can be written without deleting the written data
*6 Set the terminating resistor selector switch of the GOT in accordance with the connection type when adopting GOT multidrop connection.
*7 Note that this does not guarantee all user's operation environment. The protection is not applied when the interface environment protection cover is removed.
In addition, the product may not be used in environments under exposition of oil or chemicals for a long period of time, or in environments filled with
3.3 Power Supply Specifications
|
| Item |
| Specifications |
| |
|
| |||||
|
|
| ||||
| Input power supply voltage | 24VDC (+10% | voltage 200mV or less |
|
| |
|
|
|
|
|
| |
| Fuse | 1.6A |
|
|
| |
|
|
|
|
|
| |
| Power consumption | 7.68W (320mA/24V) | 8.40W (350mA/24V) | 7.68W (320mA/24V) | 8.40W (350mA/24V) | |
|
|
|
|
|
|
|
|
| At backlight off | 6.72W (280mA/24V) | 7.44W (310mA/24V) | 6.72W (280mA/24V) | 7.44W (310mA/24V) |
|
|
|
|
|
|
|
| Inrush current | 30A or less (26.4VDC) 2ms |
|
|
| |
|
|
|
|
|
| |
| Permissible instantaneous | Within 5ms |
|
|
| |
| power failure time |
|
|
| ||
|
|
|
|
| ||
|
|
| ||||
| Noise immunity | Noise voltage: | ||||
|
|
|
| |||
| Dielectric withstand voltage | 500VAC for 1 minute (across power supply terminals and earth) |
| |||
|
|
|
| |||
| Insulation resistance | 10M or larger by insulation resistance tester (across power supply terminals and earth) |
| |||
|
|
|
| |||
| Applicable wire size | 0.75[mm2] or more for power supply, 2[mm2] or more for grounding |
| |||
| Applicable solderless terminal | Solderless terminal for M3 screw |
| |||
|
|
|
|
|
|
|
Operation at momentary power failure
The GOT continues to operate even upon 5ms or shorter instantaneous power failure.
The GOT stops operating if there is extended power failure or voltage drop, while it automatically resumes operation as soon as the power is restored.
3. SPECIFICATIONS | 3 - 3 |
1
OVERVIEW
2
CONFIGURATION
SYSTEM
3
SPECIFICATIONS
4
PARTS NAME
5
EMC DIRECTIVE
STANDARDS AND
UL, cUL
6
INSTALLATION
7
WIRING 8
OPTION