Connecting the ground cable from the panel that houses control equipment to the panel to which the GOT is grounded
When running a single ground cable from the panel that houses such piece of control equipment as a PLC to the panel to which the GOT is grounded, the ground cable may have to be directly connected to the terminal on the GOT.
Connection cable
FG
Ground cable from the panel that houses control equipment
If electric potential difference between the ground points created by it causes malfunctions, lowering the voltage as shown in Remedy 1 below may solve the problem.
•Remedy 1 (Refer to the figures Remedy
If the electric potential difference between the ground cable and the panel that houses the GOT is creating problems, connect the ground cable to the panel also.
If the wiring method as shown in Remedy
Connection cable |
| Connection cable |
| |
|
| Ground cable from |
| |
|
| the panel that |
| |
Ground cable from |
| houses control |
| |
FG | equipment | FG | ||
the panel that | ||||
| Use the thickest |
| ||
houses control |
|
| ||
equipment |
| cable possible. |
| |
Use the thickest | Panel |
| Panel | |
cable possible. | grounding |
| grounding | |
| Remedy |
| Remedy |
If taking Remedy 1 worsens noise interference, taking Remedy 2 may alleviate it.
•Remedy 2 (Refer to the figures Remedy
Attach a ferrite core to the cable if noise from the GOT panel has adverse effects on the GOT when Remedy 1 is taken.
Wind the wire around the ferrite core several times (approx. 3 times), if a ferrite core is used. If the wiring method as shown in Remedy
Connection cable |
| Connection cable |
|
|
| Ground cable from |
|
|
| the panel that |
|
Ground cable from | FG | houses control |
|
the panel that | equipment | FG | |
houses control | Ferrite core | Use the thickest | Ferrite core |
equipment |
| cable possible. |
|
Use the thickest | Panel |
| Panel |
cable possible. | grounding |
| grounding |
| Remedy |
| Remedy |
7 - 4 | 7. WIRING |
| 7.1 Power Supply Wiring |