Connecting the ground cable from the panel that houses control equipment to the panel to which the GOT is grounded

When running a single ground cable from the panel that houses such piece of control equipment as a PLC to the panel to which the GOT is grounded, the ground cable may have to be directly connected to the terminal on the GOT.

Connection cable

FG

Ground cable from the panel that houses control equipment

If electric potential difference between the ground points created by it causes malfunctions, lowering the voltage as shown in Remedy 1 below may solve the problem.

Remedy 1 (Refer to the figures Remedy 1-1 and 1-2 below.)

If the electric potential difference between the ground cable and the panel that houses the GOT is creating problems, connect the ground cable to the panel also.

If the wiring method as shown in Remedy 1-1 is not feasible, follow Remedy 1-2.

Connection cable

 

Connection cable

 

 

 

Ground cable from

 

 

 

the panel that

 

Ground cable from

 

houses control

 

FG

equipment

FG

the panel that

 

Use the thickest

 

houses control

 

 

equipment

 

cable possible.

 

Use the thickest

Panel

 

Panel

cable possible.

grounding

 

grounding

 

Remedy 1-1

 

Remedy 1-2

If taking Remedy 1 worsens noise interference, taking Remedy 2 may alleviate it.

Remedy 2 (Refer to the figures Remedy 2-1 and 2-2 below.)

Attach a ferrite core to the cable if noise from the GOT panel has adverse effects on the GOT when Remedy 1 is taken.

Wind the wire around the ferrite core several times (approx. 3 times), if a ferrite core is used. If the wiring method as shown in Remedy 2-1 is not feasible, follow Remedy 2-2.

Connection cable

 

Connection cable

 

 

 

Ground cable from

 

 

 

the panel that

 

Ground cable from

FG

houses control

 

the panel that

equipment

FG

houses control

Ferrite core

Use the thickest

Ferrite core

equipment

 

cable possible.

 

Use the thickest

Panel

 

Panel

cable possible.

grounding

 

grounding

 

Remedy 2-1

 

Remedy 2-2