Error | Error message | Action | Channel No. | |
code | storage | |||
|
| |||
|
| The |
| |
|
| • Confirm the cable omission and status of the PLC. |
| |
|
| Channel No. is not displayed in error code or error message in the |
| |
| Communication timeout. | case an error occurs when using the |
| |
| Refer to the following manual to identify the channel No. in error. |
| ||
402 | Confirm communication pathway |
| ||
• This error may occur when the load of the PLC CPU becomes heavier |
| |||
| or modules. |
| ||
| when accessing other stations. In such a case, transfer the data of the |
| ||
|
|
| ||
|
| other stations to the host station PLC CPU and monitor them at the |
| |
|
| host. |
| |
|
| • Put COM instruction when the PLC scanning is long. |
| |
|
|
|
| |
|
| Either of the overrun error, parity bit error or flaming error was generated |
| |
| SIO status error. | when the |
| |
| Confirm the cable omission, status of the PLC.and the transmission |
| ||
403 | Confirm communication pathway |
| ||
speed of the computer link. |
| |||
| or modules. |
| ||
| Channel No. is not displayed in error code or error message in the case |
| ||
|
|
| ||
|
| an error occurs when using the |
| |
|
|
|
| |
| Specified station access is out of | • Station numbers other than master/local station are specified at the |
| |
|
| |||
406 | range. |
| ||
• A PLC CPU other than QCPU is accessed. |
| |||
| Confirm station no. |
| ||
| • Confirm the station number of the project data. |
| ||
|
|
| ||
|
|
|
| |
| Accessed other network. | • When monitoring other networks |
| |
407 | Reconfigure the [Routing Information Setting] of GT Designer3 or the |
| ||
Change network setting. |
| |||
|
| [Routing parameters] of GX Developer. |
| |
| Cannot perform operation | The operation, which could not be performed during RUN of PLC CPU, |
| |
410 | because of PLC run mode. | was performed. |
| |
| stop the PLC. | Stop the PLC CPU. |
| |
|
|
|
| |
| Memory cassette is | The memory cassette installed in the PLC CPU is EPROM or E2PROM, |
| |
411 | writeprotected. | and it is in a protected status. |
| |
| Check the memory cassette. | Confirm the memory cassette installed in PLC CPU. |
| |
|
|
|
| |
| Cannot read/write device | The key word is set in PLC CPU. |
| |
412 | protected by keyword. |
| ||
Cancel the key word. |
| |||
| Remove keyword. |
| ||
|
|
| ||
|
|
|
| |
420 | E71 specification is ASCII. | [ASCII code] is selected in [Ethernet operations] of the PLC side setting. |
| |
Select [Binary code]. |
| |||
|
|
| ||
|
|
|
| |
421 | E71 is set as | The Ethernet module on the PLC side is set in |
| |
Clear setting. | Set the Ethernet module on the PLC side to |
| ||
|
|
|
| |
| Not communicating between | PLC CPU error. Communication between PLC CPU and the PLC side |
| |
| Ethernet module impossible. |
| ||
422 | CPU and E71. Confirm CPU |
| ||
Confirm whether there is error in PLC CPU by GX Developer etc. |
| |||
| error. |
| ||
| (Confirm buffer memory) |
| ||
|
|
| ||
|
|
|
|
18 - 16 | 18. TROUBLESHOOTING |
| 18.2 Error Message and System Alarm |