Error

Error message

Action

Channel No.

code

storage

 

 

 

 

The logging setting specified in the historical trend graph setting does not

 

596

Logging setting does not exist or

exist.

 

setting value error.

Review the historical trend graph setting and specify a logging setting that

 

 

 

exists.

 

 

 

 

 

605

USB device I/F error

The error may be caused by a failure in the GOT. Please consult your

 

local Mitsubishi (Electric System) Service center or representative.

 

 

 

 

 

 

 

 

611

Improper job files.

The contents for job files are unmatched with the settings for job files.

 

Confirm job setting.

Check if there are mistakes in the settings on the setting screen.

 

 

 

 

 

 

Cannot access Logging Files

• Insert a SD card or USB memory.

 

612

• Turn on the SD card access switch.

 

Check the memory card

 

 

 

• If the SD card or USB memory have unnecessary files, delete the files.

 

 

 

• Insert a SD card or USB memory.

 

613

Error in writing logfile

• Turn on the SD card access switch.

 

 

 

• Check if the SD card or USB memory is writable.

 

 

 

 

 

 

 

• Insert a SD card or USB memory.

 

614

Error in reading logfile

• Turn on the SD card access switch.

 

 

 

• Check if the SD card or USB memory is readable.

 

 

 

 

 

 

 

The server does not work normally or the connection path to the server is

 

615

Cannot connect to MES Server.

made up incorrectly.

 

Check the Server.

• Check the operating conditions of the server.

 

 

 

• Check the network to the server.

 

 

 

 

 

 

 

The settings for the SNTP server are wrong or the network to the SNTP

 

616

Cannot connect to SNTP Server.

server is made up incorrectly.

 

Check the Server.

• Check the operating conditions of the STNP server.

 

 

 

• Check the network to the SNTP server.

 

 

 

 

 

 

 

Reconfigure the GOT (FTP client) setting.

 

640

An error occurred in a FTP client

Check the operating status and network line of the FTP server.

 

process.

For the error details, check the GOT special register GS989 (FTP

 

 

 

communication error notification).

 

 

 

 

 

800

Abnormal module status

Refer to explanations of SB0020 on the applicable network manual.

 

 

 

 

 

801

Abnormal baton passing status

Refer to explanations of SB0047 on the applicable network manual.

 

 

 

 

 

802

Abnormal cyclic transmission

Refer to explanations of SB0049 on the applicable network manual.

 

status

 

 

 

 

 

803

Transient error

Refer to explanations of SB00EE on the applicable network manual.

 

 

 

 

 

 

 

• Check if the switch settings have no error.

 

850

CC-Link switch setting error

• Check error codes stored in SW006A.

 

 

 

• Refer to explanations of SB006A on the applicable network manual

 

 

 

 

 

 

 

• Check if terminating resistors are connected.

 

 

Abnormal cyclic transmission

• Check error codes for the PLC CPU.

 

851

• Check the parameter for the PLC CPU on the master station.

 

status

 

 

 

• Check the error status of the master station.

 

 

 

• Refer to explanations of SB006E on the applicable network manual.

 

 

 

 

 

852

Abnormal host line status

• Check if the cable is unplugged or not.

 

• Refer to explanations of SB0090 on the applicable network manual.

 

 

 

 

 

 

 

 

 

 

• Check the transient error occurrence status for each station stored in

 

853

Transient error

SW0094 to SW0097.

 

 

 

• Refer to explanations of SB0094.

 

 

 

 

 

*1 When an error occurs, "FFH" is stored to the channel No.

18 - 20

18. TROUBLESHOOTING

 

18.2 Error Message and System Alarm