3.SPECIFICATIONS

3.1General Specifications

Item

 

 

Specifications

 

 

Operating ambient

Display section

0 to 50

 

 

 

 

 

 

Other than

 

 

 

 

 

 

temperature

 

0 to 55 (when horizontally installed), 0 to 50

(when vertically installed)

 

 

display section

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Storage ambient temperature

-20 to 60

 

 

 

 

 

 

 

 

 

 

Operating ambient humidity

10 to 90%, non-condensing (WBT: 39 )

 

 

 

 

 

 

 

 

 

Storage ambient humidity

10 to 90%, non-condensing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency

Acceleration

Half-

Sweep count

 

 

 

 

 

amplitude

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Conforms to

Under

5 to 8.4Hz

-

3.5mm

10 times each in

 

 

 

intermittent

 

 

 

X, Y and Z

 

 

 

 

 

 

Vibration resistance

 

JIS B 3502 and

8.4 to 150Hz

9.8m/s2

-

 

 

 

IEC 61131-2

vibration

 

 

 

directions

 

 

 

Under

5 to 8.4Hz

-

1.75mm

 

 

 

 

 

 

 

 

 

 

continuous

 

 

 

-

 

 

 

 

8.4 to 150Hz

4.9m/s2

-

 

 

 

 

vibration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shock resistance

 

Conforms to JIS B 3502, IEC 61131-2 (147 m/s2, 3 times each in X, Y and Z directions)

Operating atmosphere

Must be free of lamp black, corrosive gas, flammable gas, or excessive amount of electro

conductive dust particles and must be no direct sunlight. (Same as for saving)

 

 

 

 

 

 

 

 

 

 

 

Operating altitude *1

2000 m (6562 ft) max.

 

 

 

 

Installation location

 

Inside control panel

 

 

 

 

 

 

 

 

 

 

 

Overvoltage category *2

II or less

 

 

 

 

 

Pollution degree *3

 

2 or less

 

 

 

 

 

Cooling method

 

Self-cooling

 

 

 

 

 

 

 

 

Grounding

 

Class D grounding (100 or less), to be connected to the panel when grounding is not possible.

 

 

 

 

 

 

 

 

 

*1 Do not use or store the GOT under pressures higher than the atmospheric pressure of altitude 0m (0ft.). Failure to observe this instruction may cause a malfunction.

When the air inside the control panel is purged by pressurization, the surface sheet may be lifted by high pressure. As a result, the touch panel may be difficult to press, and the sheet may be peeled off.

*2 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power distribution network and the machinery within the premises.

Category II applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for up to the rated voltage of 300V is 2500V.

*3 This index indicates the degree to which conductive pollution is generated in the environment where the equipment is used. In pollution degree 2, only non-conductive pollution occurs but temporary conductivity may be produced due to condensation.

1