3.SPECIFICATIONS
3.1General Specifications
Item |
|
| Specifications |
|
| |||
Operating ambient | Display section | 0 to 50 |
|
|
|
|
| |
| Other than |
|
|
|
|
|
| |
temperature |
| 0 to 55 (when horizontally installed), 0 to 50 | (when vertically installed) |
| ||||
| display section |
| ||||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
Storage ambient temperature |
|
|
|
|
| |||
|
|
|
|
| ||||
Operating ambient humidity | 10 to 90%, |
|
|
| ||||
|
|
|
|
|
| |||
Storage ambient humidity | 10 to 90%, |
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
| Frequency | Acceleration | Half- | Sweep count |
|
|
|
|
| amplitude | |||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| Conforms to | Under | 5 to 8.4Hz | - | 3.5mm | 10 times each in |
|
|
| intermittent |
|
|
| X, Y and Z | |
|
|
|
|
|
| |||
Vibration resistance |
| JIS B 3502 and | 8.4 to 150Hz | 9.8m/s2 | - | |||
|
|
| IEC | vibration |
|
|
| directions |
|
|
| Under | 5 to 8.4Hz | - | 1.75mm |
| |
|
|
|
|
| ||||
|
|
|
| continuous |
|
|
| - |
|
|
|
| 8.4 to 150Hz | 4.9m/s2 | - | ||
|
|
|
| vibration |
| |||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
Shock resistance |
| Conforms to JIS B 3502, IEC | ||||||
Operating atmosphere | Must be free of lamp black, corrosive gas, flammable gas, or excessive amount of electro | |||||||
conductive dust particles and must be no direct sunlight. (Same as for saving) |
| |||||||
|
|
|
| |||||
|
|
|
|
|
| |||
Operating altitude *1 | 2000 m (6562 ft) max. |
|
|
|
| |||
Installation location |
| Inside control panel |
|
|
|
| ||
|
|
|
|
|
|
| ||
Overvoltage category *2 | II or less |
|
|
|
|
| ||
Pollution degree *3 |
| 2 or less |
|
|
|
|
| |
Cooling method |
|
|
|
|
|
| ||
|
|
| ||||||
Grounding |
| Class D grounding (100 or less), to be connected to the panel when grounding is not possible. | ||||||
|
|
|
|
|
|
|
|
|
*1 Do not use or store the GOT under pressures higher than the atmospheric pressure of altitude 0m (0ft.). Failure to observe this instruction may cause a malfunction.
When the air inside the control panel is purged by pressurization, the surface sheet may be lifted by high pressure. As a result, the touch panel may be difficult to press, and the sheet may be peeled off.
*2 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power distribution network and the machinery within the premises.
Category II applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for up to the rated voltage of 300V is 2500V.
*3 This index indicates the degree to which conductive pollution is generated in the environment where the equipment is used. In pollution degree 2, only
1
OVERVIEW
2
CONFIGURATION
SYSTEM
3
SPECIFICATIONS
4
PARTS NAME
5
EMC DIRECTIVE
STANDARDS AND
UL, cUL
6
INSTALLATION
7
WIRING 8
OPTION
3. SPECIFICATIONS | 3 - 1 |
3.1 General Specifications