Error

Error message

Action

Channel No.

code

storage

 

 

 

 

Error occurred while executing the auto repeat function of the touch

 

 

 

switch object.

 

 

Auto repeat error. Confirm

Confirm the following.

 

540

• Confirm that the other system error has not occurred during auto

 

system information.

 

 

 

repeat.

 

 

 

• Confirm that any error information is not stored in the system

 

 

 

information/GS during auto repeat.

 

 

 

 

 

 

 

The number of the set points of the recipe device exceeds the specified

 

570

Recipe device points too large.

range.

 

Put the number of the set points of the recipe device within the specified

 

 

 

 

 

 

range.

 

 

 

 

 

571

Capacity shortage of user

There is no empty area/space in D drive.

 

memory (RAM)

Format the D drive in the memory to secure free area.

 

 

 

 

 

 

 

Advanced Recipe cannot be executed for advanced recipe file with

 

581

Abnormal Advanced recipe file

incorrect contents. Delete the advanced recipe file from the SD card or

 

 

 

USB memory.

 

 

 

 

 

 

 

Cannot generate advanced recipe file. Confirm the following and execute

 

 

Cannot generate Advanced

recipe processing again.

 

582

• Confirm whether the SD card or USB memory is installed.

 

recipe file.

 

 

 

• Confirm whether the SD card access switch of the GOT is ON.

 

 

 

• Confirm the available memory of the SD card or USB memory.

 

 

 

 

 

 

Unable to save device value to

Unable to save device value to advanced recipe file.

 

583

• Confirm the write-protection of the SD card or USB memory.

 

Advanced recipe file.

 

 

 

• Confirm whether the attribute of saving file is for reading only.

 

 

 

An error has occurred during the advanced recipe file writing.

 

584

Advance recipe file save error

Do not pull out the SD card or USB memory while the Advanced Recipe

 

 

 

is operating.

 

 

 

 

 

 

 

An error has occurred during the advanced recipe file reading.

 

585

Advanced recipe file upload error

Do not pull out the SD card or USB memory while the Advanced Recipe

 

 

 

is operating.

 

 

 

 

 

586

Specified Advanced recipe

The advanced recipe of non-existing number is about to be executed.

 

number does not exist.

Execute advanced recipe of existing number.

 

 

 

 

 

587

Specified record number does

The advanced record of non-existing number is about to be executed.

 

not exist.

Execute record of existing number.

 

 

 

 

 

 

 

Saving recipe is about to be executed to the record of which recipe device

 

 

Cannot save recipe data to read

value cannot be edited.

 

588

Make the recipe device value of the record editable with Advanced

 

only record.

 

 

 

Recipe Setting of GT Designer3 or specify the record of which recipe

 

 

 

device value can be edited.

 

 

 

 

 

 

Recipe device save error. Recipe

Saving recipe is about to be executed to the advanced recipe setting that

 

589

is set for not using file.

 

file does not exist.

 

 

 

Specify the advanced recipe setting that uses file.

 

 

Recipe device upload error.

Loading recipe is about to be executed to the record of which recipe

 

590

Recipe device value does not

device value is not set.

 

 

exist.

Specify the record of which recipe device value is set.

 

 

 

 

 

 

Advanced Recipe error. Check

The advanced recipe setting is not correct.

 

591

Confirm the advanced recipe setting of the project data and download it

 

recipe data.

 

 

 

to the GOT again.

 

595

Logging file error.

Logging file error.

 

When collecting data again, delete logging files and management files.

 

 

 

 

 

 

 

 

17

INSPECTION

MAINTENANCE AND

18

TROUBLESHOOTING

APPENDICES

18. TROUBLESHOOTING

18 - 19

18.2 Error Message and System Alarm