Schneider Electric LUFP9 user manual Services of instance 16#01 of class 16#AA

Models: LUFP9

1 118
Download 118 pages 63.73 Kb
Page 112
Image 112

10. Appendix D: DeviceNet Objects

ID

Access

Name

Need

Type

Value

16#11

Get

IN total length

Optional

UINT

16#0020

This attribute indicates the total size of the input data used in the gateway’s extended memory (IN bytes supported), expressed as a number of bytes. This size is equal to the value of the previous attribute (size of inputs in DPRAM), as it only contains input data. The values of attributes 16#0F, 16#10 and 16#11 are all identical. With the LUFP9 gateway’s default configuration, the value of this attribute is equal to 32 bytes.

N.B. The gateway’s extended internal memory is different from the DPRAM memory, dealt with in the rest of this guide. As a result, when using the gateway, you will not have to worry about it.

16#12

Get

OUT cyclic I/O length

Optional

UINT

16#0020

This attribute indicates the total size of the cyclic output data (I/O OUT data), expressed as a number of bytes. This size covers all the gateway’s memory space occupied by Modbus output data, free locations also being counted. With the LUFP9 gateway’s default configuration, the value of this attribute corresponds to the size of the output area of the gateway, that is to say 32 bytes.

16#13

Get

OUT DPRAM length

Optional

UINT

16#0020

This attribute indicates the total size of the output data and parameters in the gateway’s memory (valid OUT bytes in DPRAM), expressed as a number of bytes. This size covers all of the gateway’s memory space occupied by Modbus output data and parameters, free locations also being counted. Since no output parameters are defined, the values of attributes 16#12 and 16#13 are both identical. With the LUFP9 gateway’s default configuration, the value of this attribute is equal to 32 bytes.

16#14

Get

OUT total length

Optional

UINT

16#0020

This attribute indicates the total size of the output data used in the gateway’s extended memory (OUT bytes supported), expressed as a number of bytes. This size is equal to the value of the previous attribute (size of outputs in DPRAM), as it only contains output data. The values of attributes 16#12, 16#13 and 16#14 are all identical. With the LUFP9 gateway’s default configuration, the value of this attribute is equal to 32 bytes.

N.B. The gateway’s extended internal memory is different from the DPRAM memory, dealt with in the rest of this guide. As a result, when using the gateway, you will not have to worry about it.

16#15

Get

Reserved attribute

Optional

UINT

16#0000

 

This attribute is not used.

 

 

 

16#16

Get

Application indication

Optional

USINT

(8-bit register)

This 8-bit register is reserved for the gateway’s applicative card, that is to say the card on which the AnyBus-S DeviceNet card is inserted. The various bits of this register are primarily used when internal commands of the gateway are intended to act on the gateway’s memory. These bits are not intended to be used by the DeviceNet master and will not be described here.

16#17

Get

AnyBus indication

Optional

USINT

(8-bit register)

This 8-bit register is reserved for the gateway’s AnyBus-S DeviceNet card. The various bits of this register are primarily used when internal commands of the gateway are intended to act on the gateway’s memory. These bits are not intended to be used by the DeviceNet master and will not be described here, except for bit 4:

Bit 4: This bit is set to one once the gateway’s AnyBus-S DeviceNet card has been initialized.

Services of instance 16#01 of class 16#AA

Service code

Name of the service

Need

Description

16#0E

Get_Attribute_Single

Required

This service allows to read the value of the single instance of the

 

 

 

“Diagnostic Object.”

112

Page 112
Image 112
Schneider Electric LUFP9 user manual Services of instance 16#01 of class 16#AA