The “Change-of-State / Cyclic Connection” connection (Instance ID 16#04) allows the gateway to produce its data only when their values change or when a timer called “heartbeat rate” times out. A minimum time limit is intended to prevent the connection from monopolizing the DeviceNet network’s bandwidth, should the values of the data it produces change too often. Going into “Cyclic” mode allows the number of exchanges made via this connection to be reduced if the update time (sampling) for the data produced is slow. By adjusting the connection’s cycle time to the value of this time, the produced data corresponds exactly to the data samples, without losing or repeating any sample.

Attributes of class 16#05

ID

Access

Name

Need

Type

Value

Description

 

 

 

 

 

16#01

Get

Revision

Optional

UINT

1

Revision index of the “Connection Object” class.

 

16#64

Get / Set

Polled production

Optional

USINT

0

Index of the input area used

by the gateway

for

 

 

 

 

 

 

production

on

its

“Polled

Command/Response”

 

 

 

 

 

 

connection. (1)

 

 

 

 

16#65

Get / Set

Polled consumption

Optional

USINT

0

Index of the output area used

by the gateway

for

 

 

 

 

 

 

consumption

on

its

“Polled

Command/Response”

 

 

 

 

 

 

connection. (1)

 

 

 

 

16#66

Get / Set

Strobed production

Optional

USINT

0

Index of the input area used

by the gateway

for

 

 

 

 

 

 

production on its “Bit Strobed

Command/Response”

 

 

 

 

 

 

connection. (1)

 

 

 

 

16#67

Get / Set

Strobed consumption

Optional

USINT

0

Index of the output area used

by the gateway

for

 

 

 

 

 

 

consumption on its “Bit Strobed

Command/Response”

 

 

 

 

 

 

connection. (1)

 

 

 

 

16#68

Get / Set

COS production

Optional

USINT

0

Index of the input area used

by the gateway

for

 

 

 

 

 

 

production on its “Bit Strobed

Command/Response”

 

 

 

 

 

 

connection. (1)

 

 

 

 

(1)All these 5 attributes relate to the first 5 parameters referenced by the EDS file supplied with the gateway. Write access to them (Access = Set) is reserved for DeviceNet configuration tools. You should not use the “Set_Attribute_Single” service with these attributes. An area’s index is necessarily equal to 0 and corresponds to the “Input1” area of the gateway, that is to say to its only one input data area.

Services in class 16#05

Service code

Name of the service

Need

Description

16#0E

Get_Attribute_Single

Required

This service allows to read the value of one of the class

 

 

 

attributes.

Attributes of instance 16#01 of class 16#05: Explicit Connection

ID

Access

Name

Need

Type

Value

16#01

Get

State

Required

USINT

0 to 5

This attribute represents the status of the “Explicit Connection” object. The LUFP9 gateway supports the following values: 0 (non-existent), 1 (in the process of being configured), 3 (connection established), 4 (timed out) and 5 (deferred deletion). Please see figures 5.16 and 7.4 in volume I of the DeviceNet specifications for further information on this subject.

16#02

Get

Instance type

Required

USINT

0

This attribute defines the instance’s connection type: Messaging connection (0) or I/O connection (1).

100