3. Signalling

The gateway’s 6 LEDs and the descriptive label on the removable cover which hides its block of selector switches allow you to diagnose the status of the gateway:

c

d

 

telm

 

 

 

 

 

LUFP9

 

 

f

 

n o

 

 

p q

e

 

 

 

 

r s

 

 

 

 

h

1 NETWORK STATUS

 

2 MODULE STATUS

g

3 NOT USED

 

4 NOT USED

 

 

 

 

5 MODBUS

 

 

6 GATEWAY

DeviceNet

 

LED

LED Æ Gateway state

 

 

Off: Gateway not connected to

 

 

the DeviceNet bus

 

 

Green: Gateway connected to

 

 

the DeviceNet bus:

 

 

Connection established

 

 

Red: Fatal error on connection

n

NETWORK

to the DeviceNet bus

 

STATUS

Flashing (green): Gateway

 

 

connected to the DeviceNet bus:

 

 

Connection not established

 

 

Flashing (red):Timeout in

 

 

connection to the DeviceNet bus

 

 

 The length of this timeout is

 

 

defined by the DeviceNet master

p NOT USED

Off: —

 

 

 

 

 

Off: No power

 

 

 

 

 

Flashing (green): No Modbus

 

 

communications

r MODBUS

 

Green: Modbus

 

 

communications OK

 

 

 

 

 

Red: Loss of communication with

 

 

at least one Modbus slave (1)

 

 

 

 

LED

LED Æ Gateway state

 

 

Off: No power

 

 

 

 

 

Red: Unrecoverable failure

o

MODULE

 

 

STATUS

Green: Gateway is operational

 

 

 

 

 

 

 

Flashing (red): Minor fault

 

 

q NOT USED

Off: —

 

 

 

 

 

Off: No power

 

 

Flashing (red/green):

 

 

Configuration absent / not valid

s GATEWAY

 Use AbcConf to load a valid

configuration

 

 

Green: Gateway currently being

 

 

initialized and configured

 

 

Flashing (green): Gateway is in

 

 

running order: Configuration OK

(1)The LED rMODBUS becomes red whenever you use incorrect values in the outputs corresponding to the queries of the two aperiodic services designed to read/write the value of any parameter of a Modbus slave (see chapter 4.2.8 Description of Services Assigned to Gateway Inputs/Outputs, page 31). This LED will only revert to its former green state if you reuse these very same services, but with correct values. More generally, this LED becomes red, then reverts to a green state, on loss and recovery of the communications with any Modbus slave.

N.B. If the DEVICE STATUS LED s is flashing following a sequence beginning with one or

more red flashes, we advise that you note down the order of this sequence and give this information to the Schneider Electric support service.

In some cases, all you need to do is power the gateway off then back on again to solve the problem.

22

Page 22
Image 22
Schneider Electric LUFP9 user manual Signalling