6. Configuring the Gateway

In this guide, we will be using the “AutoMap” command to establish a “raw” correspondence with all of the data from the LUFP9 gateway. We then get the correspondence shown below, derived from the one used with the gateway’s default configuration. The changes in relation to the default configuration are shown by a greyed-out background, like the “free memory locations”.

Service

PLC input

Description

Bit 0......................Bit 7

Bit 8 ...................Bit 15

Managing the downstream Modbus

I:1.1

 

LUFP9 gateway status word

network

 

(MSB Æ 16#xx••)

(LSB Æ 16#••xx)

 

 

 

I:1.2

Value of the motor starter c status register

Periodic communications

I:1.3

 

Free memory location

I:1.4

 

Value of the motor starter e status register

I:1.5

Value of the motor starter f status register

Monitoring of

I:1.6

Value of the motor starter g status register

TeSys U motor starters

I:1.7

Value of the motor starter h status register

 

I:1.8

Value of the motor starter i status register

 

I:1.9

Value of the motor starter j status register

Aperiodic communications

I:1.10

 

Free memory location

Slave no. (16#01-16#08)

I:1.11

 

Function number (16#03)

Number of bytes read (16#02)

Reading the value of a motor

I:1.12

 

Value of the

parameter read

starter parameter (RESPONSE)

 

(MSB Æ 16#xx••)

(LSB Æ 16#••xx)

 

 

Aperiodic communications

I:1.13

Slave no. (16#01-16#08)

Function no. (16#06)

I:1.14

Address of the parameter written

(MSB Æ 16#xx••)

(LSB Æ 16#••xx)

Writing the value of a motor

 

 

 

 

Value of the parameter written

starter parameter (RESPONSE)

I:1.15

(MSB Æ 16#xx••)

(LSB Æ 16#••xx)

 

 

 

Aperiodic communications

I:1.16

 

Read parameter

Write parameter

(“Trigger bytes” for the responses)

 

response counter

response counter

 

 

 

I:1.17

 

Value of the “TeSys U Status Register”

Periodic communications

I:1.18

 

Value of the “Complementary Status Register”

I:1.19

 

Value of the “K7 Status Register”

I:1.20

 

Value of the “K7 Status Register 2 (free format)”

Monitoring of

I:1.21

 

Value of the “K7 Status Register 3 (free format)”

TeSys U motor starter d

I:1.22

 

Value of the “Warning Number” register

 

I:1.23

 

Value of the “Warning Register”

 

I:1.24

 

Value of “Reserved : 2nd Warning Register”

9)Transferring the DeviceNet scanner configuration: Following the changes made to the list of DeviceNet scanner exchanges, it needs to be transferred to the DeviceNet scanner. Please see chapter 4.2.9 Transferring the DeviceNet Scanner Configuration, page 32.

6.8.4. Increasing the amount of periodic output data

E.g. “TeSys U n°4” motor starter. We are attempting to complete the control for this motor starter whilst retaining the currently controlled “Command Register” (address 704 = 16#02C0), and adding the following next register, that is to say “2st Command Register” (address 705 = 16#02C1). The number of registers controlled is therefore increased from 1 to 2.

There are quite a lot of operations to be carried out. They are described in order below:

53

Page 53
Image 53
Schneider Electric LUFP9 user manual I1.17, I1.18, I1.19, I1.20, I1.21, I1.22, I1.23, I1.24