8. Appendix B: Default Configuration

8.2. Content of the Gateway’s DPRAM Memory

The LUFP9 gateway’s DPRAM memory contains all of the data exchanged between the gateway and the 8 TeSys U motor starters, as well as two special registers only exchanged between the gateway and the DeviceNet master (words used for managing the downstream Modbus network).

The flow of data exchanged between the TeSys U motor starters, the gateway and the DeviceNet master is shown below, in order to highlight the role of the gateway’s memory in these exchanges:

TeSys U motor starters

c d e

j

8.2.1. Input Data Memory Area

Outputs

Modbus

Inputs

LUFP9 Gateway

INPUT data

memory zone

OUTPUT data memory zone

DeviceNet (SLC500) Master

Outputs

DeviceNet

Inputs

The gateway has 512 input bytes. Only the first 32 bytes are used. All of these 32 bytes make up the gateway’s input area, referenced as “Input 1” in the RsNetWorx configurator.

Service

Address

Size

Description

 

 

 

 

Managing the downstream

16#0000

1 word

Gateway status word

Modbus network

 

16#0002

1 word

Value of the motor starter c status register

 

16#0004

1 word

Value of the motor starter d status register

Periodic communications

16#0006

1 word

Value of the motor starter e status register

16#0008

1 word

Value of the motor starter f status register

Monitoring of

16#000A

1 word

Value of the motor starter g status register

TeSys U motor starters

 

 

 

16#000C

1 word

Value of the motor starter h status register

 

 

16#000E

1 word

Value of the motor starter i status register

 

16#0010

1 word

Value of the motor starter j status register

——

16#0012

1 byte

Memory location free

Aperiodic communications

16#0013

1 byte

Slave no. (16#01 to 16#08)

16#0014

1 byte

Function number (16#03)

Reading the value of a

 

 

 

16#0015

1 byte

Number of bytes read (16#02)

motor starter parameter

(RESPONSE)

16#0016

1 word

Value of the parameter read (16#xxxx)

Aperiodic communications

16#0018

1 byte

Slave no. (16#01 to 16#08)

16#0019

1 byte

Function number (16#06)

Writing the value of a

 

 

 

16#001A

1 word

Address of the parameter written (16#xxxx)

motor starter parameter

(RESPONSE)

16#001C

1 word

Value of the parameter written (16#xxxx)

Aperiodic communications

16#001E

1 byte

Read parameter response counter

(“Trigger bytes” for the responses)

16#001F

1 byte

Write parameter response counter

——

16#0020

1 byte

Free input area

(480 bytes)

 

16#01FF

1 byte

 

 

84

Page 84
Image 84
Schneider Electric LUFP9 user manual Content of the Gateway’s Dpram Memory, Input Data Memory Area