9. Appendix C: Practical Example (RSLogix 500)

Address

Symbol

Description

S:24

INDEX_SYS

Index register used in indexed addressing (prefix: ‘#’)

T4:1

TIMEOUT_WR_PARAM

Timer for the timeout of the parameter writing command

(3 seconds)

 

 

The example includes a personalized screen for monitoring the data, called “CDM 2 - WR_PAR”, in order to simplify the use of this example. The content of this screen is shown below:

Address

Symbol

Display

N7:12

WR_SLAVE

Decimal

N7:13

WR_ADDRESS

Decimal

N7:14

WR_VALUE

Decimal

B3:0/2

WR_COMMAND

Binary

 

 

 

B3:0/3

WR_RUNNING

Binary

B3:0/4

WR_OK

Binary

N7:15

WR_INDEX

Decimal

N7:16

WRPAR_1_ADDRESS

Decimal

N7:17

WRPAR_1_VALUE

Decimal

N7:18

WRPAR_2_ADDRESS

Decimal

N7:19

WRPAR_2_VALUE

Decimal

N7:20

WRPAR_3_ADDRESS

Decimal

N7:21

WRPAR_3_VALUE

Decimal

N7:22

WRPAR_4_ADDRESS

Decimal

N7:23

WRPAR_4_VALUE

Decimal

N7:24

WRPAR_5_ADDRESS

Decimal

Address

Symbol

Display

N7:25

WRPAR_5_VALUE

Decimal

N7:26

WRPAR_6_ADDRESS

Decimal

N7:27

WRPAR_6_VALUE

Decimal

N7:28

WRPAR_7_ADDRESS

Decimal

N7:29

WRPAR_7_VALUE

Decimal

N7:30

WRPAR_8_ADDRESS

Decimal

N7:31

WRPAR_8_VALUE

Decimal

O:1.13

WRPAR_SLAVE_FCT

Hexadecimal

O:1.14

WRPAR_ADRPAR

Hexadecimal

O:1.15

WRPAR_VALUE

Hexadecimal

I:1.13

CR_WRPAR_SLAVE_FCT

Hexadecimal

I:1.14

CR_WRPAR_ADRPAR

Hexadecimal

I:1.15

CR_WRPAR_VALUE

Hexadecimal

I:1.16

TRIGGER_IN_RD_WR

Hexadecimal

O:1.16

TRIGGER_OUT_RD_WR

Hexadecimal

N7:37

————

Hexadecimal

B3:0/6

————

Binary

9.5. Reserves relating to the RSLogix 500 example

This example is perfectible. So, for instance, with an incorrect response (wrong slave number, function number, etc.), the program performs no particular processing and continues to wait for a response until it times out, even though the gateway has not re-transmitted anything because, from its point of view, the response is correct. In fact, as the whole content of the Modbus response is placed in a “Data” field, it will not be checked before being copied into the gateway’s memory. Only the frame’s Checksum is checked by the gateway.

The two “trigger bytes” located in the input word I:1.16 are not used. You should use them if it is relevant for your application to be notified each time a response related to the two personalized commands “Transactions 1” and “Transactions 2” is received by the gateway.

Compatibility with the various options offered for the “Control/Status Byte” field in “ABC” (see chapter 5 Gateway Initialization and Diagnostics, page 33) is only partially dealt with in this example. The improvements required relate mainly to managing bits 14 and 15 of the DeviceNet master’s command word and the gateway’s status word (bits 6 and 7 of the corresponding input I:1.1 and output O:1.1). Also, the use of gateway diagnostics (EC and ED fields) still needs to be defined by the user.

93

Page 93
Image 93
Schneider Electric LUFP9 user manual Reserves relating to the RSLogix 500 example, Address Symbol Display