4. Software Implementation of the Gateway

4.1.2. Configuring the Motor Starters

Each motor starter should be configured as follows:

Protocol:

Modbus RTU slave

Modbus address

1 to 8

Bitrate

19,200 bits/s

Data bits

8

Start bits

1

Parity

None

Parity bit

0

Stop bits

1

When using a TeSys U motor starter with a Modbus communication module (LULC031 module), the configuration parameters for the RS485 connection are automatically detected, only the Modbus address needs to be configured.

4.1.3. Modbus cycle time

The LUFP9 gateway’s default configuration sets a cycle time of 300 ms on Modbus commands for each of the 8 TeSys U motor starters.

4.1.4. Managing degraded modes

The default management for degraded modes is described below, but it takes no account of the PLC used or of the DeviceNet scanner. Please see chapter 6.11.2.1 Managing Degraded Modes, page 65, if you would like to change the way that degraded modes for one or more Modbus commands are managed.

Desired behaviour

Reset

Outputs

Hold

Reset

Inputs

Hold

Event

DeviceNet PLC:

Disconnection of

Failure of the

Disconnection

of the downstream

the upstream

CPU stop or failure

LUFP9 gateway

Modbus RTU

DeviceNet network

 

 

network

 

 

 

Depending on the

Yes

 

 

configuration

 

Depending on the configuration of the

 

of the DeviceNet

——

TeSys U motor starters (1)

master

 

 

 

 

 

 

 

 

 

——

Depending on the configuration

Yes

 

of the DeviceNet master

——

 

 

 

 

 

 

 

 

(1) The desired behaviour with regard to the outputs should be directly configured on each of the TeSys U motor starters.

You can also read the user manuals for your master and your DeviceNet scanner to obtain further details about how to process degraded modes.

24

Page 24
Image 24
Schneider Electric LUFP9 user manual Configuring the Motor Starters, Modbus cycle time, Managing degraded modes