8. Appendix B: Default Configuration

8.2.2. Output Data Memory Area

The gateway has 512 output bytes. Only the first 32 bytes are used. All of these 32 bytes make up the gateway’s output area, referenced as “Output 1” in the RsNetWorx configurator.

Service

Address

Size

Description

 

 

 

 

Managing the downstream

16#0200

1 word

DeviceNet master command word

Modbus network

 

 

 

 

 

16#0202

1 word

Value of the motor starter ccommand register

 

16#0204

1 word

Value of the motor starter dcommand register

Periodic communications

16#0206

1 word

Value of the motor starter ecommand register

16#0208

1 word

Value of the motor starter fcommand register

Controlling

16#020A

1 word

Value of the motor starter gcommand register

TeSys U motor starters

 

 

 

16#020C

1 word

Value of the motor starter hcommand register

 

 

16#020E

1 word

Value of the motor starter icommand register

 

16#0210

1 word

Value of the motor starter jcommand register

Aperiodic communications

16#0212

1 byte

Slave no. (16#01 to 16#08)

16#0213

1 byte

Function number (16#03)

Reading the value of a

16#0214

1 word

Address of the parameter to be read (16#xxxx)

motor starter parameter (QUERY)

 

 

 

16#0216

1 word

Number of parameters to be read (16#0001)

 

Aperiodic communications

16#0218

1 byte

Slave no. (16#01 to 16#08)

16#0219

1 byte

Function number (16#06)

 

 

 

16#021A

1 word

Address of the parameter to be written

Writing the value of a

motor starter parameter (QUERY)

 

 

(16#xxxx)

 

16#021C

1 word

Value of the parameter to be written (16#xxxx)

Aperiodic communications

16#021E

1 byte

Read parameter query counter

(“Trigger bytes” for the queries)

16#021F

1 byte

Write parameter query counter

——

16#0220

1 byte

Free output area

(480 bytes)

 

16#03FF

1 byte

 

 

8.2.3. Total Number of Modbus Queries and Responses

The total number of Modbus queries and responses is equal to 36 (2 periodic queries and 2 periodic responses for each of the 8 TeSys U motor starters, plus 2 aperiodic queries and 2 aperiodic responses for all of these motor starters). Since the total number of the Modbus queries and responses one can configure for a single gateway is limited to 50, there is only 14 spare Modbus queries and responses (that is to say the equivalent of 7 Modbus commands).

So this reserve does not allow the addition of any single Modbus command for each of the TeSys U motor starters, as this would require the use of 16 Modbus queries and responses (1 query and 1 response for each of the 8 motor starters).

85

Page 85
Image 85