Operation via SNMP
13.5. Viewing AFS-16 Status via SNMP
Status of various components of the
13.6.1. Circuit Status
The status of each circuit in the system can be retrieved using the command below.
• circuitTable::circuitStatus – The status of the circuit. | |
0 | Switch Position B |
1 | Switch Position A |
155 | No Circuit Installed in this Slot |
• circuitTable::circuitReason – Returns a numeric code, which describes the | |
reason for the last successful A/B switching operation as follows: | |
0 | Power Up |
1 | User |
2 | PNA |
3 | External Alarm |
4 | Circuit Switch |
5 | Control Switch |
6 | Demo |
13.6.2. Unit Environment Status
The temperature status and Control Module Jumper status can be retrieved. The environmentUnitTable contains one row.
•environmentUnitTable::environmentUnitTemperature – The temperature of the
•environmentUnitTable::environmentUnitName – Returns the specific model number for the
•environmentUnitTable::environmentUnitMonitorAlarm – Returns the current state of the Monitor Input Signal.
0Monitor Input Signal is Low.
1Monitor Input Signal is High