CHAPTER 7: CONFIGURATION SCREEN

7.6CONNECTING/DISCONNECTING A UPS

The EMM-E6 provides the option of connecting to an Uninterruptible Power Supply (UPS) using Local Management.

To enable the UPS connection using EMM-E6/LM:

1.Use the arrow keys to highlight the COM 1 Application: field.

2.Press the Return key until “UPS” appears in the field. This field toggles between “OFFLINE”, which is the default value, “UPS”, and “SLIP”.

3.Use the arrow keys to highlight the COM 1 Baud Rate field.

4.Press the Return key until “2400 Connect?” appears in the field.

5.Use the arrow keys to highlight Connect?.

6.Press the Return key. The request “Y/N:_” appears.

7.Enter Y if you want to connect a UPS, or N if you do not want a UPS connection. Entering a Y response connects the EMM-E6 to the UPS and -- Active -- appears in the Connect? field.

8.Press the Return key.

To disable the UPS connection using EMM-E6/LM:

1.Use the arrow keys to highlight -- Active --in the COM 1 field.

2.Press the Return key. The option “Disconnect? Y/N:” appears.

3.Enter Y if you want to disconnect a UPS, or N if you want to remain connected. Entering a Y response disconnects the EMM-E6 from the UPS. -N/A- will appear in the Baud Rate field, and the COM1 Application field changes to “OFFLINE”.

4.Press the Return key.

7-8

EMM-E6 User’s Guide

Page 109