Table 4 Site Inspection Checklist (continued)

Check either Yes or No. If No, include comment number or date.

Comment or Date

8.

Is a network line available?

 

9.

Is a telephone line available?

 

10.Are customer-supplied peripheral cables and LAN cables available and of the proper type?

11. Are floor tiles in good condition and properly braced?

12.Is floor tile underside shiny or painted? If painted, judge the need for particulate test.

Power and Lighting

 

 

Number

Area or Condition

Yes

No

13.

Are lighting levels adequate for maintenance?

 

 

14.

Are AC outlets available for servicing needs (for example, laptop)?

 

 

15.

Does the input voltage correspond to equipment specifications?

 

 

15a.

Is dual source power used? If so, identify types and evaluate

 

 

 

grounding.

 

 

16.

Does the input frequency correspond to equipment specifications?

 

 

17.

Are lightning arrestors installed inside the building?

 

 

18.

Is power conditioning equipment installed?

 

 

19.

Is a dedicated branch circuit available for equipment?

 

 

20.

Is the dedicated branch circuit less than 75 feet (22.86 m)?

 

 

21.

Are the input circuit breakers adequate for equipment loads?

 

 

Safety

 

 

 

Number

Area or Condition

Yes

No

22.

Is an emergency power shutoff switch available?

 

 

23.

Is a telephone available for emergency purposes?

 

 

24.

Does the computer room have a fire protection system?

 

 

25.

Does the computer room have antistatic flooring installed?

 

 

26.Do any equipment servicing hazards exist (loose ground wires, poor lighting, and so on)?

Cooling

 

 

Number

Area or Condition

Yes No

27.Can cooling be maintained between 5°C (41 °F) and 35°C (95 °F) (up to 1,525 m/5,000 ft)? Derate 1°C/305 m (34 °F/1,000 ft) above 1,525 m/5,000 ft and up to 3,048 m/10,000 ft.

28.Can temperature changes be held to 5°C (9 °F) per hour with tape media? Can temperature changes be held to 20°C (36 °F) per hour without tape media?

29.Can humidity level be maintained at 40% to 55% at 35°C (95 °F) noncondensing?

30. Are air-conditioning filters installed and clean?