Maintenance Commands and Trouble-Clearing Aids

Page8-333test customer-alarm

8
test customer-alarm

This command performs hardware diagnostic tests on the leads of the Processor

and EPN maintenance circuit packs, used for customer-provided alarms b y

closing the appropriate relay for 1 minute. Failure is verified by checking t he

customer alarm attached to the specified circuit pack.

1. If no alarms are registered against the maintenance o bject then the test sequenc e is run only once. The
long clear
option forces a clear of al l alarms if no errors are en countered during testing. The
short clear
option only clears
alarms pertinent to tests in th e short sequence.
2. Refer to the Report Scheduler an d System Printer feature specifi cation for more details.
Action/Object Qualifier Qualifier Description Permissions Defaults Feature
Interactions
test
customer-alarm
location
short
long
repeat
number
clear
schedule
Extension of the data module o r
data channel to be tested (per
dial-plan)
Runs test number 115
Runs test number 115 (sam e as
short test option)
How many times each test in the
sequence is repeated (1- 100)
This option causes the test
sequence (short or long) to repeat
until the alarm (if any) is cleared or
a single test in the sequenc e fails.1
Command is validated and th en a
scheduling form displays to
schedule execution of th e
command. The command is then
placed in the command queue an d
is executed at the specified time.
The information displayed by the
command is sent to the system
printer instead of the screen.2
Examples:
test customer-alarm
test customer-alarm schedule
test customer-alarm 02 r 2
test customer-alarm 01b r 25
test customer-alarm 01b r 25
schedule
test customer-alarm 2a
test customer-alarm 2a sh
test customer-alarm 01b l
schedule
test customer-alarm 3 c
init
inads
craft
See
below none