DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si
555-230-123
Issue 1
April 1997
Maintenance Object Repair Procedures
Page10-1074PI-SCI (System Communication Interface)
10
Error Log Entries and Test to Clear Values
1. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the
appropriate test description and follow the recommended procedures.
2. See WARNING below.
!WARNING:
The "test interface long" command resets the PI-BD and causes all ISDN-PRI and BX.25 links to come down.
3. Major alarms may be downgraded to Warning alarms based on the value used in the set options
command.
Table 10-313. PI-SCI System Communication Interface Error Log Entries
Error
Type Aux
Data Associated Test Alarm Le vel On/Off
Board Test to Clear Value
010 Any Any Any test interface PCS sh r 1
1 (a) 2055
2056
2057
2058
none none none none
257 (b) Any none MAJOR ON test interface PCS l2
769 (c) Any none MAJOR/
WARNING3OFF test interface PCS l2
1025 (d) Any none MAJOR/
WARNING3OFF test interface PCS l2
1281 (e) Any Sci Start Test (#176) MAJOR/
WARNING3OFF test interface PCS l2
1793 (f) Any none MAJOR ON test interface PCS l2
2049 (g) 90xx Sci Start Test (#176) M AJOR ON test interface PCS l2
2305 (f) Any Sci Self Test (#231) MAJOR ON test interface
PCS sh r 2
2561 (h) Any none MAJOR/
WARNING3OFF test interface PCS l2
2817 (i) Any none MAJOR/
WARNING3OFF test interface PCS l2
2818 (j) Any none MAJOR/
WARNING3OFF test interface PCS l2
3073 (f) Any none MAJOR/
WARNING3OFF test interface PCS l2