DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si
555-230-123
Issue 1
April 1997
Maintenance Object Repair Procedures

Page10-1135POWER (Battery & Battery Charger for DC-Powered Systems

10
Note:
a. This error occurs only in a multi-carrier cabinet and can be ignored but not cleared for DC-powered systems.
System Technician-Demanded Tests:
Descriptions and Error Codes
Always investigate tests in the order presented in the table below when inspecting errors in the system. By clearing error codes associated with the
Battery & Battery Charger Query Test,
for example, you may also clear errors generated from other tests in the testing sequence.
1. Run the Short Test Sequence first. If all t ests pass, run the Long Test S equence. Ref er to t he appropr iate
test description and follow the recommended procedures.
1. D = Destructive; ND = Nondestructive
769 Any Battery & Battery Charger
Query Test (#5) (Error Code 2) MINOR ON test environment P sh r 1
3840
(a) 1005
or
1028
Assoc. Test Battery & Battery
Charger Query Test (#5) ON
Order of Investigati on Short Test
Sequence Long Test
Sequence D/ND1
Battery & Battery Charger Query
Test (#5) X X ND
AC Power Query Test (#78) (a) X X ND
Emergency Transfer Query Test (#124) (c) X X ND
Cabinet Sensors Query Test (#122) (d) X X ND
External Alarm Lead Query Test (#120) (e) X X ND
Analog Ring Generator Initialization Test (#117) (f) X X ND
Analog Ring Generator Query Test (#118) (f) X X ND
Table 10-333. Power Error Log Entries Continued
Error
Type Aux
Data Associated Test Al arm
Level On/Off
Board Test to Cl ear Value
Continued on next page