UPS OPERATING INSTRUCTIONS

8.On the System Status screen, select the UPM command.

9.On the UPS Control Command screen, select the UPM 1 command.

10.Press the CONTROLS pushbutton on the System Status menu bar. The UPM 1 Control Command screen is displayed.

11.On the UPM 1 Control Command screen, select UPM ON.

12.Press the SELECT pushbutton on the UPM 1 Command menu bar.

13.Verify the following messages display sequentially on the UPM status line:

DC STARTING, CHARGER OFF INVERTER STARTING INVERTER SYNCING

READY

The UPM 1 rectifier and inverter turn on.

If the Inherent Redundancy option is enabled, a loss of redundancy alarm will be issued. Silence the alarm and continue to Step 14.

14.Repeat Steps 8 through 12 selecting UPM 2 to start UPM 2.

15.Observe the following messages are displayed sequentially on the UPM status line:

DC STARTING, CHARGER OFF INVERTER STARTING INVERTER SYNCING

READY

The UPM 2 rectifier and inverter turn on.

16.Repeat Steps 8 through 12 selecting UPM 3 to start UPM 3.

17.Verify the following messages display sequentially on the UPM status line:

DC STARTING, CHARGER OFF INVERTER STARTING INVERTER SYNCING

READY

The UPM 3 rectifier and inverter turn on. When the inverter reaches full voltage, the UPS is ready to transfer to the Normal mode and supply the critical load.

18.If the UPS is a Plus 1 model, repeat Steps 8 through 12 selecting UPM 4 to start UPM 4.

19.Verify the following messages display sequentially on the UPM status line:

DC STARTING, CHARGER OFF INVERTER STARTING INVERTER SYNCING

READY

The UPM 4 rectifier and inverter turn on. When the inverter reaches full voltage, the UPS is ready to transfer to the Normal mode and supply the critical load.

7−22

EATON Powerware® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com

Page 164