UPS INSTALLATION PLAN AND UNPACKING

Table 3-13.Power Cable Conduit Requirements (continued)

UPS Model

Voltage

Terminal

Number of Wires

Minimum Conduit

Number of

in Conduit

Trade Size

Conduits

 

 

 

 

 

 

 

 

 

 

 

AC Input to UPS Rectifier

4

3

5

 

 

(A, B, C, Ground)

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to UPS Rectifier (Separate Feed)

4

2

3

 

 

(A, B, C, Ground)

(Each UPM)

 

 

 

 

 

400 Vac

 

 

 

 

 

AC Input to Bypass and Output (Four Wire)

4

3

4

 

 

 

 

(A, B, C, Ground)

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to Bypass and Output (Five Wire)

5

3

5

 

 

(A, B, C, Neutral, Ground)

 

 

 

 

 

 

 

 

 

 

 

Powerware 9395−825/825

 

AC Input to UPS Rectifier

4

3

4

 

(A, B, C, Ground)

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to UPS Rectifier (Separate Feed)

4

2

2

 

 

(A, B, C, Ground)

(Each UPM)

 

 

 

 

 

480 Vac

 

 

 

 

 

AC Input to Bypass and Output (Four Wire)

4

3

4

 

 

 

 

(A, B, C, Ground)

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to Bypass and Output (Five Wire)

5

3

5

 

 

(A, B, C, Neutral, Ground)

 

 

 

 

 

 

 

 

 

 

 

 

DC

Battery

 

See Note

 

 

(Positive, Negative, Ground)

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE Select conduit taking into consideration the DC input wire sizes listed in Table 3-4on page 3−9 or Table 3-5on page 3−10, the DC terminations listed in Table 3-9on page 3−13, type of battery installation, and requirements from NEC Table 4, Electrical Metallic Tubing (EMT).

External overcurrent protection and disconnect are not provided by this product, but are required by codes. Refer to Table 3-4on page 3−9, Table 3-5on page 3−10, or Table 3-6on page 3−11 for wiring requirements. If an output lockable disconnect is required, it is to be supplied by the customer.

Table 3-14lists the recommended rating for input circuit breakers.

Table 3-15lists the recommended rating for input circuit breakers with separate rectifier inputs UPS. A separate breaker is required for each UPM.

Table 3-14. Recommended Input Circuit Breaker Ratings

UPS Model

 

Input Rating

 

 

 

 

Load Rating

400V

480V

 

 

 

 

 

 

80% Rated

1600A

1200A

Powerware 9395−825/650

 

 

 

100% Rated

1200A

1000A

 

 

 

 

 

 

80% Rated

1600A

1600A

Powerware 9395−825/750

 

 

 

100% Rated

1600A

1200A

 

 

 

 

 

 

80% Rated

2000A

1600A

Powerware 9395−825/825

 

 

 

100% Rated

1600A

1200A

 

 

 

 

 

3−16

EATON Powerware® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com

Page 38
Image 38
Powerware 650825 kVA Power Cable Conduit Requirements, Recommended Input Circuit Breaker Ratings, UPS Model Input Rating