Chapter 10

Product Specifications

10.1Model Numbers

The UPS is housed in a free-standing cabinet, divided into two sections with safety shields behind the door and front panels. The UPS is available in 50 or 60 Hz with various output power ratings.

Models

Power Rating

Frequency

 

 

 

Powerware 9395−825/650

650 kVA

50/60 Hz

 

 

 

Powerware 9395−825/750

750 kVA

50/60 Hz

 

 

 

Powerware 9395−825/825

825 kVA

50/60 Hz

 

 

 

The following sections detail the input, output, environmental, and battery specifications for the UPS.

10.2 Specifications

10.2.1 UPS Input

Operating Input Voltage

400 Vac

 

480 Vac

Operating Input Frequency Range

50/60 Hz

 

 

Operating Input Current

See Table 3-4on page 3−9, Table 3-5on page 3−10, or Table 3-6on

 

page 3−11.

 

Reduced for Generator

 

Adjustable

Input Current Harmonic Content

5% THD at full load

 

 

Power Factor

Minimum 0.99

 

 

Line Surges

6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801-4

 

 

Battery Voltage

480 Vdc

 

 

Battery Charging Capacity

Configurable per UPM at nominal line voltage:

 

Up to 120A with less than 85% load

 

Up to 80A with 100% load

 

 

Battery Shunt Trip

48 Vdc

 

 

EATON Powerware® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com

10−1

Page 187
Image 187
Powerware 650825 kVA operation manual Model Numbers, Specifications, UPS Input