UPS INSTALLATION PLAN AND UNPACKING

Table 3-1. UPS Cabinet Weights

 

 

 

Weight

Model

Section

 

kg (lb)

 

 

 

 

Shipping

Installed

 

 

 

 

 

ISBM

1498 (3302)

1390 (3064)

Powerware 9395−825/650

 

 

 

UPM

1590 (3505)

1482 (3267)

 

 

 

 

 

 

ISBM

1498 (3302)

1390 (3064)

Powerware 9395−825/750

 

 

 

UPM

1590 (3505)

1482 (3267)

 

 

 

 

 

 

ISBM

1498 (3302)

1390 (3064)

Powerware 9395−825/825

 

 

 

UPM

1590 (3505)

1482 (3267)

 

 

 

 

 

The UPS cabinet uses forced air cooling to regulate internal component temperature. Air inlets are in the front of the cabinet and outlets are in the top. Allow clearance in front of and above each cabinet for proper air circulation. The clearances required around the UPS cabinet are shown in Table 3-2.

Table 3-2. UPS Cabinet Clearances

From Top of Cabinet

457.2 mm (18") minimum clearance for ventilation

 

 

From Front of Cabinet

914.4 mm (36") working space

 

 

From Back of Cabinet

None Required

 

 

From Right Side of Cabinet

152.4 mm (6") working space

 

 

From Left Side of Cabinet

None Required

 

 

The basic environmental requirements for operation of the UPS are:

S Ambient Temperature Range:

0–40°C (32–104°F)

SRecommended Operating Range: 20–25°C (68–77°F)

S Maximum Relative Humidity:

95%, noncondensing

C A U T I O N

If battery systems are located in the same room as the UPS, the battery manufacturer’s environmental requirements should be followed if they are more stringent than the UPS requirements. Operating temperatures above the recommended range will result in decreased battery life and performance, and may reduce or void the battery warranty.

The UPS ventilation requirements are shown in Table 3-3.

Table 3-3. Air Conditioning or Ventilation Requirements During Full Load Operation

Rating

Input/Output

Heat Rejection

Ventilation Required for

Voltage

BTU/hr  1000 (kg−cal/hr)

Cooling Air Exhaust

 

 

 

 

 

 

400/400

125 (31613)

 

650 kVA

 

 

 

480/480

127 (31933)

 

 

 

 

 

 

Approximately 2265 liter/sec (4800 cfm)

 

400/400

145 (36476)

 

 

750 kVA

 

 

With Field Installed UPM:

480/480

146 (36845)

 

 

 

 

Approximately 3020 liter/sec (6400 cfm)

 

400/400

159 (40124)

 

 

825 kVA

 

 

 

480/480

161 (40530)

 

 

 

 

 

 

 

3−2

EATON Powerware® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com

Page 24