UPS INSTALLATION PLAN AND UNPACKING

Table 3-15. Separate Rectifier Input Recommended Input Circuit Breaker Ratings

UPS Model

Input Rating for Each UPM

 

 

Load Rating

480V

 

 

 

 

Powerware 9395−825/650

80% Rated

500A

Powerware 9395−825/750

 

 

100% Rated

400A

Powerware 9395−825/825

 

 

 

C A U T I O N

To reduce the risk of fire, connect only to a circuit provided with maximum input circuit breaker current ratings from Table 3-14in accordance with the NEC, ANSI/NFPA 70.

The line-to-line unbalanced output capability of the UPS is limited only by the full load per phase current values for AC output to critical load shown in Table 3-4on

page 3−9 or Table 3-5on page 3−10. The recommended line-to-line load unbalance is 50% or less.

Bypass and output overcurrent protection and bypass and output disconnect switches are to be provided by the customer. Module Output Breakers (MOBs) are to be provided by the customer. Table 3-16lists the recommended rating for bypass, output, and MOB circuit breakers.

Table 3-16. Recommended Bypass, Output, and MOB Circuit Breaker Ratings

UPS Model

 

Output Rating

 

 

 

 

Load Rating

400V

480V

 

 

 

 

 

 

80% Rated

1200A

1000A

Powerware 9395−825/650

 

 

 

100% Rated

1000A

800A

 

 

 

 

 

 

80% Rated

1600A

1200A

Powerware 9395−825/750

 

 

 

100% Rated

1200A

1000A

 

 

 

 

 

 

80% Rated

1600A

1600A

Powerware 9395−825/825

 

 

 

100% Rated

1200A

1000A

 

 

 

 

 

EATON Powerware® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com

3−17