Chapter 4

UPS System Installation

4.1Preliminary Installation Information

W A R N I N G

Installation should be performed only by qualified personnel.

Refer to the following while installing the UPS system:

SChapter 3 for cabinet dimensions, equipment weight, wiring and terminal data, and installation notes.

SDo not tilt the cabinets more than "10° during installation.

SRemove the conduit landing plates to add conduit landing holes as required. Plate material is 16 gauge steel (1.5 mm/0.06" thick).

SIf perforated floor tiles are required for ventilation, place them in front of the UPS.

4.2Unloading the UPS Sections from the Pallet

The ISBM and UPM sections are bolted to separate wooden pallets supported by wood skids. To remove the pallets:

W A R N I N G

The UPS sections are heavy (see Table 3-1on page 3−2). If unpacking and unloading instructions are not closely followed, the cabinets may tip and cause serious injury.

C A U T I O N

SDo not tilt cabinets more than 10° from vertical.

SLift the cabinets only with a forklift or damage may occur.

To prevent damage to the wiring channel and wiring in the UPM section base when lifting or moving the cabinet:

SLift and move the UPM section using only the front or rear forklift slots.

SVerify that the forklift forks are in a horizontal position before inserting them into the forklift slots. DO NOT angle fork tips upward.

SInsert the forks all the way through the base. DO NOT insert forks partially into the base to move the cabinet.

SForks may be partially inserted into the front or rear forklift slots for minor positioning if the forks are kept in a horizontal position with no upward angling.

SDO NOT use the forklift slots on the end of the cabinet to move the cabinet.

SEnd forklift slots may be used for minor positioning if the forks are kept in a horizontal position with no upward angling.

If these instructions are not followed, damage to the wiring channel and wiring will occur.