UPS

 

 

 

TB1

 

 

Battery Aux

5

 

Battery Aux Common

6

48 Vdc Battery Shunt Trip +

7

 

48 Vdc Battery Shunt Trip –

8

 

 

 

NOTE Battery aux and DC shunt trip wiring should be a minimum of 18 AWG.

UPS SYSTEM INSTALLATION

Battery

Disconnect

48 Vdc

ST

Figure 4-31. Typical Battery Interface Connection – Common Battery System

 

 

UPM 1

UPM 2

UPM 3

 

 

Battery

Battery

Battery

 

UPS

Disconnect

Disconnect

Disconnect

 

TB1

 

 

 

Battery Aux

5

 

 

 

Battery Aux Return

6

 

 

 

48 Vdc Battery Shunt Trip +

7

 

 

 

 

48 Vdc

ST

ST

ST

48 Vdc Battery Shunt Trip

8

 

 

 

NOTE Battery aux and DC shunt trip wiring should be a minimum of 18 AWG.

Figure 4-32. Typical Battery Interface Connection – Separate Battery System

UPM 4

Battery

Disconnect

ST

EATON Powerware® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com

4−37

Page 83
Image 83