COMMUNICATION

8.10Supervisory Contact Module II

An optional Supervisory Contact Module II (SCM II) establishes an interface between the UPS system and the customer’s monitor. This interface allows the customer to monitor operational status of the UPS system equipment. The SCM II can be flush-mounted or surface-mounted on a desktop, or secured to a wall. Figure 8-5shows the SCM II.

Figure 8-5. Supervisory Contact Module II Enclosure

The SCM II provides signals for the indications shown in Table 8-3.

Table 8-3. SCM II Status Indicators and Connections

Indication

TB2 Connections

 

 

SYSTEM NORMAL

TB2-1 through TB2-3

 

 

NO REDUNDANCY

TB2-4 through TB2-6

 

 

ON GENERATOR

TB2-7 through TB2-9

 

 

BYPASS NOT AVAILABLE

TB2-10 through TB2-12

 

 

ON BATTERY

TB2-13 through TB2-15

 

 

UPS ALARM

TB2-16 through TB2-18

 

 

ON BYPASS

TB2-19 through TB2-21

 

 

SHUTDOWN IMMINENT

TB2-22 through TB2-24

 

 