UPS INSTALLATION PLAN AND UNPACKING
EATON Powerware® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com
3−14
Table 3-10. Supplied External Wiring Terminal Hardware Kit
Part Size Quantity Terminals Used On Eaton Part Number
Bolt, Grade 5 M10 x 25 mm 15 Ground 180190078−087
Bolt, Grade 5 M12 x 45 mm 92 Rectifier Input, Bypass Input, Battery Input,
Output, and Neutral 180190078−113
Flat Washer M10 15 Ground 180500036−100
Flat Washer M12 184 Rectifier Input, Bypass Input, Battery Input,
Output, and Neutral 180500036−120
Conical Washer M10 15 Ground 180500037−100
Conical Washer M12 92 Rectifier Input, Bypass Input, Battery Input,
Output, and Neutral 180500037−120
Nut M12 92 Rectifier Input, Bypass Input, Battery Input,
Output, and Neutral 180200001−07
Table 3-11. Recommended Installation Parts and Tools (Not Supplied by Eaton)
Part Size Quantity Manufacturer Part Number Notes
Long Barrel 2-Hole Lug
2/0 AWG
As required
Thomas & Betts 54862BE
Copper wire only
3/0 AWG Thomas & Betts 54864BE
4/0 AWG Thomas & Betts 54866BE
250 MCM Thomas & Betts 54868BE
300 MCM Thomas & Betts 54870BE
350 MCM Thomas & Betts 54872BE
400 MCM Thomas & Betts 54874BE
500 MCM Thomas & Betts 54876BE
Manual Hydraulic Crimp Tool 14 Ton 1Thomas & Betts TBM14M
Die Set N/A 1 Thomas & Betts 15506
Table 3-12. Separate Rectifier Input UPM Power Cable Terminations for the Powerware 9395−825/650, 9395−825/750, and 9395−825/825
Terminal Function Terminal Function Size of Pressure Termination Tightening Torque
Nm (lb ft) Type Screw
AC Input to each UPM Rectifier
E1 Phase A 2 − #6−250 kcmil 42.4 (375) 5/16" Hex
E2 Phase B 2 − #6−250 kcmil 42.4 (375) 5/16" Hex
E3 Phase C 2 − #6−250 kcmil 42.4 (375) 5/16" Hex