UPS INSTALLATION PLAN AND UNPACKING

Table 3-10. Supplied External Wiring Terminal Hardware Kit

Part

Size

Quantity

Terminals Used On

Eaton Part Number

 

 

 

 

 

Bolt, Grade 5

M10 x 25 mm

15

Ground

180190078−087

 

 

 

 

 

Bolt, Grade 5

M12 x 45 mm

92

Rectifier Input, Bypass Input, Battery Input,

180190078−113

Output, and Neutral

 

 

 

 

 

 

 

 

 

Flat Washer

M10

15

Ground

180500036−100

 

 

 

 

 

Flat Washer

M12

184

Rectifier Input, Bypass Input, Battery Input,

180500036−120

Output, and Neutral

 

 

 

 

 

 

 

 

 

Conical Washer

M10

15

Ground

180500037−100

 

 

 

 

 

Conical Washer

M12

92

Rectifier Input, Bypass Input, Battery Input,

180500037−120

Output, and Neutral

 

 

 

 

 

 

 

 

 

Nut

M12

92

Rectifier Input, Bypass Input, Battery Input,

180200001−07

Output, and Neutral

 

 

 

 

 

 

 

 

 

Table 3-11. Recommended Installation Parts and Tools (Not Supplied by Eaton)

Part

Size

Quantity

Manufacturer

Part Number

Notes

 

 

 

 

 

 

 

2/0 AWG

 

Thomas & Betts

54862BE

 

 

 

 

 

 

 

 

3/0 AWG

 

Thomas & Betts

54864BE

 

 

 

 

 

 

 

 

4/0 AWG

 

Thomas & Betts

54866BE

 

 

 

 

 

 

 

 

250 MCM

 

Thomas & Betts

54868BE

 

Long Barrel 2-Hole Lug

 

As required

 

 

Copper wire only

300 MCM

Thomas & Betts

54870BE

 

 

 

 

 

 

 

 

 

 

350 MCM

 

Thomas & Betts

54872BE

 

 

 

 

 

 

 

 

400 MCM

 

Thomas & Betts

54874BE

 

 

 

 

 

 

 

 

500 MCM

 

Thomas & Betts

54876BE

 

 

 

 

 

 

 

Manual Hydraulic Crimp Tool

14 Ton

1

Thomas & Betts

TBM14M

 

 

 

 

 

 

 

Die Set

N/A

1

Thomas & Betts

15506

 

 

 

 

 

 

 

Table 3-12. Separate Rectifier Input UPM Power Cable Terminations for the Powerware 9395−825/650, 9395−825/750, and 9395−825/825

Terminal Function

Terminal

Function

Size of Pressure Termination

Tightening Torque

Type Screw

Nm (lb ft)

 

 

 

 

 

 

 

 

 

 

 

 

E1

Phase A

2 − #6−250 kcmil

42.4 (375)

5/16" Hex

 

 

 

 

 

 

AC Input to each UPM Rectifier

E2

Phase B

2 − #6−250 kcmil

42.4 (375)

5/16" Hex

 

 

 

 

 

 

 

E3

Phase C

2 − #6−250 kcmil

42.4 (375)

5/16" Hex

3−14

EATON Powerware® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com

Page 36
Image 36
Powerware 650825 kVA operation manual Supplied External Wiring Terminal Hardware Kit