TB1

TB2

TB3

UPS SYSTEM INSTALLATION

UPS

REPO NC

 

REPO Return

 

REPO NO

1

REPO Return

 

Battery Aux

 

Battery Aux Common

 

Battery Shunt Trip +

 

Battery Shunt Trip –

10

Output Contactor K3 NC Aux

Output Contactor K3 NC Aux Common

 

1

Pull Chain

 

Pull Chain Common

Alarm Relay NC

Alarm Relay Common

Alarm Relay NO

10

Alarm Relay Common

 

UPS

 

Building Alarm 1

1

Building Alarm 1 Return

Building Alarm 2

 

 

Building Alarm 2 Return

 

Building Alarm 3

 

Building Alarm 3 Return

 

Building Alarm 4

10

Building Alarm 4 Return

 

 

Building Alarm 5

 

Building Alarm 5 Return

NOTE All building alarm inputs require an isolated normally−open or normally−closed contact or switch (rated at 24 Vdc, 20 mA minimum) connected between the alarm input and common terminal as shown. Building alarm inputs can be programmed for use with either normally−open or normally−closed contacts. All control wiring and relay and switch contacts are customer-supplied.

NOTE The building alarms can be programmed to display the alarm functional name.

NOTE A jumper wire must be connected between pins 1 and 2 on TB1, if the normally−closed REPO contact is not used.

Figure 4-30. Terminal Blocks TB1, TB2, and TB3 Connector Assignments

EATON Powerware® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com

4−35

Page 81
Image 81
Powerware 650825 kVA operation manual Repo Return, Battery Aux Common, Battery Shunt Trip +, Building Alarm