UPS SYSTEM INSTALLATION
4.Locate the external wiring terminal hardware kit packed on the bottom left side of the ISBM section.
5.If installing an UPS with separate rectifier feeds, proceed to Step 6; otherwise, proceed to Step 8.
NOTE On an UPS that is configured for separate rectifier inputs all sources that feed the separate rectifier inputs must be derived from a common ground point.
6.Connect phase A, B, and C rectifier input power wiring from the utility source to each UPM rectifier input terminal block in the UPS cabinet. See paragraph 3.2.2 on page 3−8, Table
7.Proceed to Step 9.
8.Using hardware from the external wiring terminal hardware kit (see Table
9.If installing an UPS configured as an Input Output Module (IOM), proceed to Step 11; otherwise, proceed to Step 10.
10.Using hardware from the external wiring terminal hardware kit (see Table
11.If wiring a distributed bypass system, proceed to Step 12; otherwise, proceed to Step 14.
C A U T I O N
Distributed bypass system wiring length should be in accordance with Figure
12.Using hardware from the external wiring terminal hardware kit (see Table
13.Proceed to paragraph 4.8.2.
14.Using hardware from the external wiring terminal hardware kit (see Table
paragraph 3.2.2 on page 3−8 for wiring and termination requirements.
15.Proceed to paragraph 4.8.2.
EATON Powerware® 9395 UPS | 4−21 |