UPS OPERATING INSTRUCTIONS

7.3Single UPS Operation

NOTE A Field Installed UPM (FI−UPM) is always designated as UPM 4.

7.3.1Starting the UPS in Normal Mode

To start the UPS system:

1.If the UPS contains input breaker CB1, verify that input breaker CB1 is open.

2.Close the UPS input feeder circuit breaker.

3.Close the UPS Bypass input feeder circuit breaker.

4.Observe the UPS control panel display becoming active, indicating logic power.

5.Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed.

6.On the System Status screen, verify the UPS status is SHUTDOWN and the UPM status is OFFLINE.

7.Close the battery breaker.

8.If the UPS contains input breaker CB1, close input breaker CB1.

9.On the System Status screen, select the UPS command.

10.Press the CONTROLS pushbutton on the System Status menu bar. The UPS Control Command screen is displayed.

11.On the UPS Control Command screen, select GO TO NORMAL.

12.Press the SELECT pushbutton on the UPS Command menu bar.

If Auto Bypass is enabled (factory default), the critical load is immediately supplied by the bypass source, in Bypass mode, until the inverter turns on and the UPS transfers to Normal mode. The status indicator on the UPS control panel indicates the UPS is in Bypass mode. If Auto Bypass is not enabled, the UPS output remains off until the UPS transfers to Normal mode.

13.Verify the following messages display sequentially on the UPM status line:

DC STARTING, CHARGER OFF INVERTER STARTING INVERTER SYNCING ONLINE, CHARGING

The rectifier and inverter turn on. The inverter continues to ramp up to full voltage.

Once the inverter reaches full voltage, the UPS output contactor K3 closes and the static switch turns off. Power is now supplied to the critical load in Normal mode. It takes approximately one minute for the UPS to achieve Normal mode.

The NORMAL status indicator is illuminated. The UPS status indicates ONLINE. The UPM status indicates ONLINE, CHARGING.